12.5 Tightening Torques for Cover Screws
Enclosure size and class
Cable cover screws (Nm)
Screws on the cover of the AC drive (Nm)
FR4/FI4 IP54
2.2
0.7
FR5 IP21/ IP54
2.2
0.7
FR6/FI6 IP21/ IP54
2.2
0.7
FR7/FI7 IP21/ IP54
2.4
0.8
FR8/FI8 IP54
0.8 Nm
(1)
0.8
FR9
0.8
0.8
1
The cover of the power unit.
12.6 Tightening Torques of the Terminals
Table 31: Tightening Torques of the Terminals
Enclosure size
Drive type
Tightening torque (Nm)
Tightening torque (lb-in.)
FI4
0004 2–0012 2
0003 5–0012 5
0.5–0.6
4.5–5.3
FI6
0038 5–0061 5
0004 6–0034 6
10
88.5
FI7
0072 5–0105 5
0041 6–0080 6
10
88.5
FI8
0140 5
0062 6–0100 6
20
(1)
354
1
Tightening torque of terminal connection to the insulative base is 9 Nm
12.7 Power Ratings
12.7.1 Overload Capability
The
low overload
means that if 110% of the continuous current (I
L
) is required for 1 minute every 10 minutes, the remaining 9 minutes
must be approximately 98% of I
L
or less. This is to make sure that the output current is not more than I
L
during the duty cycle.
Specifications
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
118 | Danfoss A/S © 2019.07