10.11 Technical Data, VACON® 100 FLOW
Table 51: Technical Data of the VACON
®
100 FLOW AC Drive
Technical item or
function
Technical item or function
Technical information
Mains connection
Input voltage U
in
208–240 V, 380–500 V, 525–600 V, 525–690 V, -10%… +10%
Input frequency
50–60 Hz, -5...+10%
Connection to mains
Once per minute or less
Starting delay
6 s (MR4-MR6)
8 s (MR7-MR9)
Network imbalance
Max ±3% of the nominal voltage
Mains
Mains types: TN, TT, and IT
Short circuit current: the maximum short circuit current must be < 100 kA.
Motor connection
Output voltage
0-U
in
Continuous output current
I
L
: Ambient temperature max. +40 °C overload 1.1 x I
L
(1 min/10 min)
Output frequency
0–320 Hz (standard)
Frequency resolution
0.01 Hz
Control character-
istics
Switching frequency (see pa-
rameter P3.1.2.3)
200–500 V
MR4-MR6:
•
1.5–10 kHz
•
Default: 6 kHz (except for 0012 2, 0031 2, 0062 2, 0012 5, 0031 5 and
0061 5: 4 kHz)
MR7-MR9:
•
1.5–6 kHz
•
Default: MR7: 4 kHz, MR8: 3 kHz, MR9: 2 kHz
600–690 V
MR5-MR9:
•
1.5–6 kHz
•
Default: 2 kHz
•
For a product that is configured for a C4 installation on IT network the
maximum switching frequency is limited to default 2kHz.
Automatic switching frequency derating in case of overload.
Frequency reference:
•
Analog input
•
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
8–320 Hz
Acceleration time
0.1–3000 s
Deceleration time
0.1–3000 s
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
138 | Danfoss A/S © 2019.05