32 of 165
M-SV-VT-001-EN Rev. A
Figure 18 - IFV Actuator
Compressor Components
3.2.2.1 Removal and
Installation
Figure 19 - IFV Actuator
Mounting Set Screws
Set Screw - 3 Nm (27
in.lb.) (3 places)
IFV Actuator Removal:
1. Isolate the Compressor power as described in the
“Electrical Isolation of the Compressor/VFD”
section of this manual.
2. Disconnect the Red (power) and Black (signal) cables from the IFV by turning the collars, located
on the cable ends, in a counter-clockwise rotation.
3. Using a 2.5 mm hex bit, loosen the three (3) set screws that attach the IFV Actuator to the
Bonnet/Function Module.
4. Remove the IFV Actuator.