![Danfoss TR 6 Installation Manual Download Page 1](http://html1.mh-extra.com/html/danfoss/tr-6/tr-6_installation-manual_3853471001.webp)
Installation guide
Thermostatic expansion valve
Type TR 6
067
R9
50
8
067
R9
50
8
© Danfoss I DCS (sw) I 2015.12
DKRCC.PI.AN0.A5.02 / 520H8512
| 1
Max. working pressure:
PS / MWP = 42 bar / 610 psig
Max. test pressure:
47 bar / 680 psig
Reverse: B
→
A
Flow direction:
Q
nom.
A
→
B [kW / TR] = 100%
Q
nom.
B
→
A [kW / TR] = 80%
Adjustable setting
Fixed setting
Max. 100 °C / 210 °F
Max. 130 °C / 265 °F
R22 / R407C: Max. 100 °C / 210 °F
R410A: Max. 75 °C / 167 °F
Short-lived peak 150 °C / 300 °F
Dan
fo
ss
67-74.11
A
B
A
B
Min. 5% Ag
Refrigerants:
R22/R407C and R410A
Normal: A
→
B