5.2 Schematic diagram
DH
Supply
HE
Supply
DH
Return
HE
Return
TRL
TFL
Your substation might look different than the schematic diagram shown.
Schematic description
A Heat exchanger, HE
10 Circulator pump
26 Pressure gauge
1
Ball valve
14 Sensor pocket, energy meter
31 Differential pressure controller
4
Safety valve
18 Thermometer
38 Expansion tank
7
Thermostatic valve, HE
20 Filling/drain valve
41 Fitting piece, energy meter
9
Strainer
24 Delivered loose with unit
48 Air vent, manual
DH Supply:
District Heating Supply
DH Return:
District Heating Return
HE Supply:
Heating Supply
HE Return:
Heating Return
TFL:
Tank Flow Line
TRL:
Tank Return Line
5.2.1
Technical parameters
Technical parameters
Nominal pressure:
PN 10 (PN 16 versions are available on enquiry)
Max. DH supply temperature:
120 °C
Brazing material (HEX):
Copper
Heat exchangers test pressure:
30 bar
Sound level:
≤ 55 dB
AQ221686472754en–010401 / LUK4030601
© Danfoss | 2022.11 | 11