background image

7.3 Troubleshooting HE

Problem

Possible cause

Solution

Too little or no heat.

Strainer clogged in DH or HE circuit
(radiator circuit).

Clean gate/strainer(s).

The filter in the energy meter on DH circuit
clogged.

Clean the filter (after consulting the DH
plant operator).

Defective or wrongly adjusted differential
pressure controller.

Check the operation of the differential
pressure controller – clean the valve seat if
required.

Sensor defective – or possibly dirt in the
valve housing.

Check the operation of the thermostat –
clean the valve seat if required.

Automatic controls, if any, wrongly set or
defective - possibly power failure.

Check if the setting of the controller
is correct – see separate instructions.
Check the power supply. Temporary
setting of motor to “manual” control – see
instructions on automatic controls.

Pump out of operation.

Check if the pump is receiving power and
that it turns. Check if there is air trapped in
the pump housing – see pump manual.

The pump is set at too low speed of
rotation.

Set the pump at higher speed of rotation.

Pressure drop – the pressure drop on
the radiator circuit shows lower than
recommended operating pressure.

Fill water on the system and check the
functioning of the pressure expansion
vessel if required.

Air pockets in the system.

Vent the installation thoroughly.

Limiting of the return temperature adjusted
too low.

Adjust according to instructions.

Defective radiator valves.

Check – replace.

Uneven heat distribution in building
because of incorrectly set balancing valves,
or because there are no balancing valves.

Adjust/install balancing valves.

Diameter of pipe to substation too small or
branch pipe too long.

Check pipe dimensions.

Uneven heat distribution.

Air pockets in the system.

Vent the installation thoroughly.

DH supply temperature too high.

Wrong setting of thermostat or of
automatic controls, if any.

Adjust automatic controls, – see
instructions for automatic controls.

Defective controller. The controller does
not react as it should according to the
instructions.

Call automatic controls manufacturer or
replace the regulator.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

DH supply temperature too low.

Wrong setting of automatic controls, if any.

Adjust automatic controls – see instructions
for automatic controls.

Defective controller. The controller does
not react as it should according to the
instructions.

Call in automatic controls manufacturer or
replace controller.

Defective sensor on self-acting thermostat.

Replace thermostat – or sensor only.

Wrong placement/fitting of outdoor
temperature sensor.

Adjust location of outdoor temperature
sensor.

Strainer clogged.

Clean gate/strainer.

VI.CW.Y5.02 / LUK42260

© Danfoss | 2019.01 | 19

Operating Guide Termix VMTD MIX Compact 28

Summary of Contents for Termix VMTD MIX Compact 28

Page 1: ...up 6 4 3 Electrical connections 7 5 0 Design 8 5 1 Design 8 5 2 Schematic diagram 9 6 0 Controls 10 6 1 Heating circuit 10 6 2 DHW temperature control 13 6 3 Other 15 6 4 Maintenance 16 7 0 Troublesh...

Page 2: ...conditions for radiator thermostats in order to enable individual temperature control in each room nThe mixing loop creates a suitable temperature level for the heating system Domestic hot water DHW T...

Page 3: ...the substation inform the operating personnel and call for expert help immediately REACH All Danfoss A S products fulfill the requirements in REACH One of the obligations in REACH is to inform custom...

Page 4: ...2 District heating DH return 3 Heating HE supply 4 Heating HE return 5 Domestic hot water DHW 6 Domestic cold water DCW 7 Hot water circulation HWC Connection sizes DH HE G 1 int thread DCW DHW G 1 i...

Page 5: ...bstation pipes and connections should be cleaned and rinsed Tightening Due to vibration during transport all substation connections must be checked and tightened before installation Unused connections...

Page 6: ...thighten connections After water has been added to the system and the system has been put into operation re tighten ALL connections Pump The pump must be switched off during system fill Under floor he...

Page 7: ...st be electrically connected so that it can be disconnected for repairs Outdoor temperature sensor Outdoor sensors should be mounted so as to avoid exposure to direct sunlight They should not be place...

Page 8: ...er DHW 11 Domestic hot water pump 30 Flow controller with integrated control valve F Electronic controller 25 Pressure gauge with ball valve 48 Air vent manual 2 Single check valve 27A Actuator HE 10...

Page 9: ...19 Surface sensor 40 Immersion sensor 9 Strainer 24 Delivered loose with unit 48 Air vent manual 10 Circulator pump DHW Domestic Hot Water DCW Domestic Cold Water HWC Hot Water Circulation DH Supply...

Page 10: ...ntrolled by the HE temperature controller 6 1 3 AVTB controller 30 100 The temperature setting is as follows 1 35 C 2 55 C 3 75 C 4 95 C 5 100 C The values are intended as a guide Thermostatic control...

Page 11: ...closes when set max flow is exceeded and can be used in combination with Danfoss electrical actuators with or with out safety function Spring return motor can be used as safety function by power fail...

Page 12: ...elected via user interface EuP 2015 Ready The MAGNA3 circulator pumps are designed for circulating liquids in heating systems with variable flows where you want to optimise the setting of the pump dut...

Page 13: ...atures of up to 90 C Thermostatic control DHW temperature is adjusted as follows To increase temperature turn the handle on the thermostatic controller to select a higher number To decrease temperatur...

Page 14: ...in the event of power failure 6 2 4 Domestic hot water pump Important It is necessary to mount a domestic hot water circulation pump on the water heater to avoid regulation problems The circulation pu...

Page 15: ...should be cleaned regularly by authorized personnel The frequency of cleaning would depend on operating conditions and the manufacturer s instructions VI CW Y5 02 LUK42260 Danfoss 2019 01 15 Operatin...

Page 16: ...H supply temperature and DHW temperature Connections Checking all connections for leakages Safety valves The operation of the safety valves should be checked by turning the valve head in the indicated...

Page 17: ...re of the DH is at the normal level summer at least 60 C winter at least 70 C the differential pressure is equal to or higher than the normal local differential pressure in the DH network if in doubt...

Page 18: ...tle or no DHW Defective controller Check replace DCW is being mixed with the DHW e g in a defective thermostatic mixing valve Check replace Hot water in some taps but not in all Defective or clogged n...

Page 19: ...the installation thoroughly Limiting of the return temperature adjusted too low Adjust according to instructions Defective radiator valves Check replace Uneven heat distribution in building because o...

Page 20: ...e pipe loop The system should feature electronic controls as well as return sensors Pump pressure too high Adjust pump to a lower level Air in system Vent the system Defective or incorrectly set radia...

Page 21: ...should be dismantled and its components sorted if possible in various groups before recycling or disposal Always follow the local disposal regulations VI CW Y5 02 LUK42260 Danfoss 2019 01 21 Operatin...

Page 22: ...22 Danfoss 2019 01 VI CW Y5 02 LUK42260 Operating Guide Termix VMTD MIX Compact 28...

Page 23: ...8 0 Declaration 8 1 Declaration of conformity Category 0 with electrical equipment VI CW Y5 02 LUK42260 Danfoss 2019 01 23 Operating Guide Termix VMTD MIX Compact 28...

Page 24: ...24 Danfoss 2019 01 VI CW Y5 02 LUK42260 Operating Guide Termix VMTD MIX Compact 28...

Reviews: