Installation guide

Pressure switch

 

RT 5, RT 110, RT 112, RT 116, RT 117, RT 121, RT 200 

017

R9

31

5

017

R9

31

5

© Danfoss | DCS (jmn) | 2015.11

IC.PI.P10.C5.53 | 520B7012 | 1

Danfos

s

17-5027.10

1 m Cu

7

/

16

 - 20 UNF

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Fig. 7

ENGLISH

Data

Pressure switch, types RT 5, RT 110, 

RT 112, RT 117, RT 121, RT 200, RT 116

Max. test pressure

RT 110, RT 112, RT 121:  

8 bar

RT 5, RT 116, RT 200:  

25 bar

RT 117:  

47 bar

Fitting

A set of Pg13.5 cable gland is attached to 

the RT in a separate bag. To ensure IP66 

(units with automatic reset) or IP54 (units 

with external reset) grade of RT enclosure 

it is necessary to assemble this gland as 

shown in the fig. 2. If this gland is not used 

with a cable, a metal blinding should be also 

assembled.

Damp out strong pressure pulsations. 

A damping coil, fig. 3 or fig. 4, will often be 

sufficient.

Insert a water-filled tube loop as a 

temperature lock (e.g. a 10 mm Cu tube) if at 

high plant temperatures there is a risk that 

the pressure connection of the control will 

become heated to more than 100 °C.

Position the pressure control so that on 

water plant it cannot be exposed to frost. It 

can operate on an air cushion, for example.

Setting

The pressure controller is set by rotating the 

knob (5), at the same time reading the main 

scale (9). See fig. 1.

The differential is set by rotating the 

differential adjusting nut (19) to the value 

indicated by the use of the nomogram in 

fig. 6. The maximum operating pressure is 

thus the sum of the setting pressure and the 

differential.

Example

It is desired to control the pressure in an 

oilfired steam boiler by the use of an RT 116. 

Maximum pressure 9 bar. 

Minimum pressure 8.2 bar. 

Differential 9 - 8.2 = 0.8 bar.

1.  Connect the oil burner to terminals 1-2 

  of the pressure switch.

2.  Set the pressure switch for 8.2 bar by 

  rotating the knob (5).

3.  Set the differential adjusting nut (19) at 

  the figure 7 which is found by reading  

  the nomogram in fig. 6.

DANSK

Code no.

017xxxx

Code no.

060-333366

Code no.

060-007166

Data

Pressostater type  RT 5, RT 110, RT 112, 

RT 117, RT 121, RT 200, RT 116

Max. prøvetryk

RT 110, RT 112, RT 121:  

8 bar

RT 5, RT 116, RT 200:  

25 bar

RT 117:  

47 bar

Montering

Et sæt Pg13,5 kabelforskruning er vedlagt

produktet i en separat pose. For at sikre

kapslingsgrad IP66 (enheder med automatisk 

reset) eller IP54 (enheder med ekstern DANSK 

RESET) er det nødvendigt at montere denne 

kabelforskruning som vist i fig. 3. Hvis denne 

kabelforskruning ikke bruges sammen med 

et kabel, bør der monteres en blindprop 

(metal skive).

Dæmp kraftige trykpulsationer. Ofte er 

dæmpesløjfe fig.3 eller fig. 4 tilstrækkelig.

Indskyd en vandfyldt rørsløjfe som 

temperaturspærre, fx af10 mm Cu-rør, hvis 

der i anlæg med høje temperaturer er risiko 

for at pressostatens tryktiIslutning kan 

opvarmes til over 100 °C.

Anbring pressostaten, så den ved vandanlæg 

ikke udsættes for frost (lad den fx ar-bejde på 

en luftpude).

Indstilling

Pressostaten indstilles efter. den funktion - 

slutte eller bryde - som skal ske ved faldende 

tryk (områdeindstilling).

Selve indstillingen udføres med hånd- 

Reviews: