Instructions
RMT-230, RMT-230T

Fig. 1

Fig. 2

Fig. 3

T

ss

Rp

4

1 3 2

t

N

L

T

1 3 2

t

N

L

T

ss

Rp

4

1 3 2

t

N

L

6

5

Rn

Fig. 4

Fig. 5

Fig. 6

Fig. 7

Fig. 8

Location, Fig. 1

Do not site the room thermostat in a draught, in 
direct sunlight or close to appliances giving off 
heat (e.g. television set.)

Fixing, Fig 2 and 3

Make  sure  the  supply  voltage  to  the  system  is 
disconnected  before  commencing  installation 
or  subsequentially  removing  the  thermostat 
cover.

Fix  the  base  moulding  on  a  flush  box.  The 
temperature  range  can  be  limited  by  moving 
the two springs on the back of the setting dial, 
Fig 4.

Wiring, Fig 5, 6 and 7

Switch function: SPDT, Fig 8
230 V, 50 - 60 Hz, 10 (4) A
Min. contact load: 150 mA

Note: Always connect the live (L) to terminal 

.

When the room thermostat is connected to an 
inductive load, without noise suppression, there 
might be risk of radio and TV interference.

RMT  versions  with  parallel  accelerator  Rp,  will 
have  a  lower  temperature  differential  when 
terminal 

 is connected as shown in Fig. 6 and 

7.

RMT-230T only

RMT-230T will set back the temperature by 5K, 
when the built-in resistance Rn is connected as 
shown in Fig. 7.

Note:

A  means  of  disconnecting  the  supply  with  a 
contact separation of at least 3mm in all poles 
must  be  incorporated  in  the  fixed  wiring, 
according  to  BS  3955.  This  product  does  not 
require an earth connection.

ENGLISH

RMT230

RMT230

RMT230T

087R9127

087R9127