6.5 Electrical Installation in General
NOTE
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors required, (60-75
°
C) recommended.
Power (kW)
Torque (Nm)
Frame
1 x 200-240 V 3 x 200-240 V 3 x 380-480 V
Line
Motor
DC connection/Brake
Control Terminals
Earth
Relay
M1
0.18 - 0.75
0.25 - 0.75
0.37 - 0.75
1.4
0.7
Spade
1)
0.15
3
0.5
M2
1.5
1.5
1.5 - 2.2
1.4
0.7
Spade
1)
0.15
3
0.5
M3
2.2
2.2 - 3.7
3.0 - 7.5
1.4
0.7
Spade
1)
0.15
3
0.5
M4
11.0-15.0
1.3
1.3
1.3
0.15
3
0.5
M5
18.5-22.0
1.3
1.3
1.3
0.15
3
0.5
1)
Spade connectors (6.3 mm Faston plugs)
Table 6.2 Tightening of Terminals
How to Install
VLT Micro Drive Design Guide
46
MG02K102 - VLT
®
is a registered Danfoss trademark
6