background image

24 Volt d.c.

ONLY

Quick Start Guide
ICAD 600/900/1200

Ref.

Colour

Description

A

Black

Common Alarm

B

Brown

ICM fully open

C

Red

ICM fully closed

D

Orange

GND ground

E

Yellow

+

0/4 - 20 mA Input

F

Green

+

0/2-10V input or digital 
input for on/off control

G

Blue

+

0/4 - 20 mA Output

I

Black

+

Fail safe supply
Battery / UPS* 19 V d.c.

II

White

+

Supply voltage
24 V d.c.

III

Brown

Digital 
Ouput

Uninterruptable Power Supply

Terminal box - 

not supplied 

by Danfoss

1

2

3

24 Volt d.c.

ONLY

© Danfoss A/S (AC-SMC/MWA), 05 - 2011

 

DKRCI.PI.HV0.J2.02 / 520H4887 / 027R9801 

 

1

Before you

start using ICAD:

Tighten CW

Quick Start Guide

Oil