Installation guide
Pressure control
Type MBC 5000
© Danfoss A/S (AC-MCI / jmn), 2013-06
IC.PI.P10.B2.22 / 520B5758
1
06
1R
931
4
06
1R
931
4
Electrical connection
Attention:
Use only the accompanying plug,
also when replacing.
Caution:
Disconnect power supply before wiring connenctions
are made to avoid possible electrical shock
or damage to equipment. All wiring should conform
to the National Electrical Code and local regulations.
Contact load
2.9 FLA/17.4 LRA 240AC/60Hz
Pilot duty 278VA 240VAC/60Hz
Adjustment
Mechanical differential. One full turn (360°) of the MBC
setting-screw is approx. equal to 7% of the full setting range.
Type
Range
Permissible
operating pressure
Code no
High pressure
diaphragm
73 – 580 psi
1088 psi
061B301666
High pressure
piston
232 – 2320 psi
4350 psi
061B503266
Operation
temperature
Piston version: -40 – 140 °F
Diaphragm version: 14 – 140 °F
Maximum media
temperature
185 °F