background image

Installation guide

Pressure control

Type MBC 5000

© Danfoss A/S (AC-MCI / jmn), 2013-06 

IC.PI.P10.B2.22 / 520B5758   

1

06

1R

931

4

06

1R

931

4

Electrical connection

Attention: 

Use only the accompanying plug,  

also when replacing.

Caution: 

Disconnect power supply before wiring connenctions  

are made to avoid possible electrical shock  

or damage to equipment. All wiring should conform  

to the National Electrical Code and local regulations.

Contact load

2.9 FLA/17.4 LRA 240AC/60Hz

Pilot duty 278VA 240VAC/60Hz

Adjustment

Mechanical differential. One full turn (360°) of the MBC 

setting-screw is approx. equal to 7% of the full setting range.

Type

Range

Permissible  

operating pressure

Code no

High pressure 

diaphragm

73 – 580 psi

1088 psi

061B301666

High pressure 

piston

232 – 2320 psi

4350 psi

061B503266

Operation 

temperature

Piston version:                 -40 – 140 °F

Diaphragm version:         14 – 140 °F

Maximum media 

temperature

185 °F