Installation guide

Pressure switch

Type KP 21

© Danfoss A/S (AC-MCI / jmn), 2013-11 

 IC.PI.P10.G3.02 / 520B5881 

1

06

0R

94

10

06

0R

94

10

Ambient temperatures

 

 

                   Caution: Do not mount a switch in a position where 

                  dirt, sediment or oil will affect the operation of the switch.

Enclosure

                                             

                               CAUTION: The mounting panel must be plane to avoid damage of switch.

Low pressure (LP) side setting

CUT-IN minus DIFFERENTIAL equals CUT-OUT

     Test pressure (p 

test

)

High pressure (HP) side setting

CUT-OUT minus DIFFERENTIAL equals CUT-IN

P

test

 max.

20 bar P

e

P

test

 max.

20 bar P

e

LP           

HP

1.  Adjust range spindle to

  desired CUT-IN value

2.  Adjust differential 

  spindle to desired 

 DIFFERENTIAL

  (DIFF.) value

LP

scale

1.   Adjust range spindle to

 

desired CUT-OUT value.

2.   DIFFERENTIAL (DIFF.)

 

is fixed.

 

Value printed on scale plate.

t

l

 min. 

−40°C (−40°F)

 

 

−25ºC (−13ºF)

t

max  

   65ºC (150ºF)

HP

scale