4
Configuration
4.1
Configuring the Ethernet Interface
The X1 and X2 interfaces are internally connected with an Ethernet switch and share the same physical MAC layer, and the same IP
settings apply to both interfaces. IPv4 settings are configured in MyDrive®Insight or in the control panel.
1.
Configure IPv4 settings.
–
In MyDrive® Insight, go to
Setup and Service
>
Interface configuration
>
Interface X1/X2
>
IPv4 settings
.
–
In the control panel, navigate to parameter group
10.2 Communication Interfaces
.
Table 14: IPv4 Settings
Function
Value
Description
Interface X1/X2 MAC
address
00:1B:08:xx:xx:xx
The MAC address of interface X1/X2. The value is read-only.
Disable
Only link-local IP address in the 169.254.xxx.xxx range is active.
Static IP
A static IP address is entered manually.
Automatic
IP address is assigned via a DHCP or BOOTP server.
IPv4 addressing
method
DCP (default)
DCP is used with PROFINET where a PLC assigns the IP address, subnet
mask, and other relevant parameters.
Requested IPv4 ad-
dress
xxx.xxx.xxx.xxx
If
Automatic
is selected as the IPv4 addressing method and no DHCP/
BOOTP server is present, the X1/X2 interface automatically configures
an IP address and subnet mask in the 169.254.xxx.xxx range.
Requested IPv4 sub-
net mask
xxx.xxx.xxx.xxx
The requested IPv4 subnet mask for the interface.
Requested IPv4 gate-
way address
xxx.xxx.xxx.xxx
Requested IPv4 gateway address for the interface.
Enable
Enable ACD
Disable (default)
Request to enable or disable Address Conflict Detection for the inter-
face.
The change does not take effect before a power cycle is performed. If
no conflicts are detected, ACD activity shows 0. If an address conflict
occurs, the ACD activity shows 1, and the IPv4 interface reverts to an
automatically assigned IP address in the 169.254.xxx.xxx range.
The recommended setting for PROFINET is
Disable
.
DNS server 1, 2
xxx.xxx.xxx.xxx
The user-requested Domain Name Server 1 for the interface (for man-
ual IP addressing mode only).
4.2
Configuring Name of Station
1.
Navigate to parameter
Name of Station
(parameter number
7080
).
28
| Danfoss Drives Oy © 2024.04 AQ481922043454en-000101 / 172K4282A
Operating Guide | iC7-Marine PROFINET