background image

Shut-off ball valve  for R744 (45 bar/650 psi)

Type GBC 6s to GBC 54s 

009R9517

009R9517

Installation guide

© Danfoss | DCS (sw) | 2017.03 

 

 

 

DKRCC.PI.FB0.C5.02 | 1 

Temperature range:

    

-40 – 150 °C / -40 – 300 °F

Max. working pressure (PS/MWP):
45 bar/650 psi

Remove access cap (if present)

OPEN position

CLOSED position

Refrigerant:   R744 (CO

2

)

Opening valve

Single-flow

1

2

Valve size

Max. Torque

Nm

ft-lbs

6s - 22s

5.2

28s

17 

12.6

35s

20 

14.8

42s - 54s

34

25.2

 

Warning: Only authorized persons are allowed to operate this valve, as closing    

 

can cause build-up of excessive pressure in the system.

For the application use with R744 as part of a secondary loop or cascade system should 

refer to the datasheet for more attentions.

Applicable to all common non-flammable refrigerants, excluding R717. Also for noncorrosive
gases/liquids dependent on sealing material compatibility. 
The design pressure shall not be less than the value outlined in Section 9.2 of ANSI/ASHRAE 15