background image

VD.UI.A1.12       © Danfoss 09/2006

1

Compression fittings

Code no.

Compression fittings

Code  no.

PEX 15x2.5 mm

013G414700

ALUPEX 14x2 mm

013G418400

PEX 16x2.2 mm

013G416300

ALUPEX 16x2 mm

013G418600

PEX 18x2.5 mm

013G415900

ALUPEX 18x2 mm

013G418800

PEX 20x2.5 mm

013G416100

ALUPEX 20x2 mm

013G419000

Spare parts

Code  no.

Gland seal for FHV-A

013G029000

Gland seal for FHV-R

013U007000

Accessories

Code  no.

Mounting tool/installation aid with integral spirit level

003L133800

Bleed key

087N684900

Anti theft plugs for RA2000 sensors

(50 pcs)

013G123200

Threaded range limiting pins for RA2000 sensors

(30 pcs)

013G123700

Toolkit, comprising allen key for RA2000 sensors

013G123600

Round front cover for FHV-R/A

                                                                          

     003L105000

Square frontcover for FHV-R/A

003L105200

Extension  piece for RA sensors

17,9 mm

003L103500

Extension piece for FJVR sensors

17,9 mm

 003L103600

Type

Description

Connection   kvs (m

3

/h)

Code no.

FHV-R

Valve with air vent & bleed key

 G 3/4" A

0.88

003L100000

FHV-R

Valve with air vent, bleed key & drain hose

 G 3/4" A

0.88

003L100300

FJVR

Return temp. limiter sensor. Setting range 10 -50 °C

003L104000

FJVR

Return temp. limiter sensor. Setting range 10 -80 °C

003L107000

Data sheet

FHV regulating valve

Temperature control of individual floor-heated rooms
or mixed floor-heating/radiator systems

Application

Ordering and  technical data

FHV control valves are ideally suited to the tem-
perature control of individual under-floor heated
rooms and for systems using floor-heating in con-
junction with radiators. Danfoss offers the following
versions:

- the FHV-R provides temperature control of under-
floor heating circuits, using a return temperature
limiting valve fitted with a type FJVR sensor ele-
ment

- the FHV-A enables floor temperature control via a
pre-settable thermostatic valve fitted with a type RA
2000 sensor element

Note: If using the FHV-A for room temperature con-
trol, the flow temperature should not be permitted to
exceed the maximum recommended by the floor
heating supplier. When the FHV-R is used for con-
trolling floor heating, the heated floor area should
not be greater than 10 m

2

.

FHV control valves are flexible to use and can be
simply and easily installed in the floor heating cir-
cuit.

With the FHV-A, its integral pre-setting simplifies
hydraulic balancing of the system. Connections to
the 3/4" external thread are made with Danfoss
compression connectors.

FHV-R.

 Set includes wall enclosure box, cover and valve (return temperature limiter). An FJVR sensor ele-

ment is required for controlling the return temperature.

FHV-A.

 Set includes wall enclosure box, cover and pre-settable valve. A type RA2000 sensor element is

required for controlling the room temperature.

FHV-R

FHV-A

Type

Description

Connection   kvs (m

3

/h)

Code no.

FHV-A

Valve with air vent & bleed key

 G 3/4" A

0.04-0.79

003L100100

FHV-A

Valve with air vent, bleed key & drain hose

 G 3/4" A

0.04-0.79

003L100400

RA2010 Room temperature sensor. Setting range 5-26 °C

013G201000

RA2070 Room temperature sensor. Setting range 5-22 °C

013G207000

Max. operating pressure

6 bar

Max. differential pressure

0,6 bar

Test pressure

10 bar

Max. flow temperature

90 

°

C