11.2 Mains Supply
P110
P132
P160
P200
P250
Typical Shaft output at
400 V [kW]
110
132
160
200
250
Typical Shaft output at
460 V [HP]
150
200
250
300
350
Enclosure IP21
D1
D1
D2
D2
D2
Enclosure IP54
D1
D1
D2
D2
D2
Enclosure IP00
D3
D3
D4
D4
D4
Output current
Continuous
(at 400 V) [A]
212
260
315
395
480
Intermittent (60 s
overload)
(at 400 V) [A]
233
286
347
435
528
Continuous
(at 460/480 V) [A]
190
240
302
361
443
Intermittent (60 s
overload)
(at 460/480 V) [A]
209
264
332
397
487
Continuous KVA
(at 400 V) [KVA]
147
180
218
274
333
Continuous KVA
(at 460 V) [KVA]
151
191
241
288
353
Continuous
(at 400 V) [A]
204
251
304
381
463
Continuous
(at 460/480 V) [A]
183
231
291
348
427
Max. cable size, mains
motor, brake and load
share [mm
2
(AWG
2)
)]
2 x 70
(2 x 2/0)
2 x 70
(2 x 2/0)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
Max. external pre-fuses
[A]
1
300
350
400
500
630
Estimated power loss
at rated max. load [W]
4)
,
400 V
3234
3782
4213
5119
5893
Estimated power loss
at rated max. load [W]
4)
,
460 V
2947
3665
4063
4652
5634
Weight,
enclosure IP21, IP54 [kg]
96
104
125
136
151
Weight,
enclosure IP00 [kg]
82
91
112
123
138
Efficiency
4)
0.98
Output frequency
0-800 Hz
Heatsink overtemp. trip
90
°
C
110
°
C
110
°
C
110
°
C
110
°
C
Power card ambient trip
60
°
C
Table 11.1 Mains Supply 3x380-480 VAC
Specifications
VLT® Refrigeration Drive 110-250 kW Operating Instructions
68
MG16F102 - VLT® is a registered Danfoss trademark
11
11