13-10 Comparator Operand
Array [6]
Option:
Function:
[196] Digital input x46
4
[197] Digital input x46
5
[198] Digital input x46
6
[199] Digital input x46
7
13-11 Comparator Operator
Array [6]
Option:
Function:
Select the operator to be used in the
comparison. This is an array parameter
containing comparator operators 0 to 5.
[0]
<
Select < [0] for the result of the evaluation to
be TRUE, when the variable selected in
is smaller than the
fixed value in
13-12 Comparator Value
. The
result will be FALSE, if the variable selected in
is greater than the
fixed value in
13-12 Comparator Value
.
[1]
*
= (equal)
Select ≈ [1] for the result of the evaluation to
be TRUE, when the variable selected in
is approximately
equal to the fixed value in
13-12 Comparator
Value
.
[2]
>
Select > [2] for the inverse logic of option <
[0].
[5]
TRUE longer
than...
[6]
FALSE
longer
than...
[7]
TRUE
shorter
than...
[8]
FALSE
shorter
than...
13-12 Comparator Value
Array [6]
Range:
Function:
Application
dependent
*
[-100000.000 -
100000.000 N/A]
Enter the ‘trigger level’ for
the variable that is
monitored by this
comparator. This is an array
parameter containing
comparator values 0 to 5.
3.14.4 13-2* Timers
Use the result (TRUE or FALSE) from
timers
directly to define
an
event
(see
13-51 SL Controller Event
), or as Boolean input in
a
logic rule
(see
13-40 Logic Rule Boolean 1
,
13-42 Logic Rule
Boolean 2
or
13-44 Logic Rule Boolean 3
). A timer is only FALSE
when started by an action (i.e., Start timer 1 [29]) until the
timer value entered in this parameter is elapsed. Then it
becomes TRUE again.
All parameters in this parameter group are array parameters
with index 0 to 2. Select index 0 to program Timer 0, select
index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the value to define the
duration of the FALSE output
from the programmed timer. A
timer is only FALSE if it is started
by an action (i.e.,
Start timer 1
[29]) and until the given timer
value has elapsed.
Parameter Descriptions
FC 300 Programming Guide
3-112
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3