FC 300 Profibus
Parameters
8-55 Set-up Select
Option:
Digital input
[0]
Bus
[1]
Logic AND
[2]
*
Logic OR
[3]
Function:
Choose between controlling the drive via the
terminals (digital input) and/or via the bus.
If you select
Bus
, you can only activate Selection
of Setup if it is transmitted via the serial
communication port or fieldbus option. If you select
Logic AND
, you must also activate the command via
one of the digital inputs. If you select
Logic OR
,
you can also activate the Set-up command via one
of the digital inputs.
NB!:
This parameter is active only when par.
8-01
Control Site
is set to [0]
Digital and
control word
.
8-56 Preset Reference Select
Option:
Digital input
[0]
Bus
[1]
Logic AND
[2]
*
Logic OR
[3]
Function:
Choose between controlling the drive via the
terminals (digital input) and/or via the bus.
If you select
Bus
, you can only activate the Preset
Reference command if it is transmitted via the serial
communication port or fieldbus option. If you select
Logic AND
, you must also activate the command via
one of the digital inputs. If you select
Logic OR
, you
can also activate the Preset Reference command via
one of the digital inputs.
NB!:
This parameter is active only when par.
8-01
Control Site
is set to [0]
Digital and
control word
.
8-90 Bus Jog 1 Speed
Range:
0. - par. 4-13 RPM
*
100.
RPM
Function:
Sets a fixed speed (jog) activated via the serial port
or bus option.
8-91 Bus Jog 2 Speed
Range:
0. - par. 4-13 RPM
*
200.
RPM
Function:
Sets a fixed speed (jog) is activated via the serial
port or bus option