Danfoss EKD 316 Manual Download Page 8

If the superheat fluctuates

When the refrigerating system has been made to work steadily, 

the controller’s factory-set control parameters should in most 

cases provide a stable and relatively fast regulating system.

If the system, however, fluctuates this may be due to the fact that 

superheat parameters that are too low have been selected. Before 

starting any adjustment of the factory settings check the S2 sensor 

location – see page 9:

If adaptive superheat has been selected (n21 = 1):

Adjust: n09, n10 and n18.

If load-defined superheat MSS has been selected (n21 = 2):

Adjust: n09, n10 and n22.

Alternatively it may be due to the fact that the set regulation 

parameters are not optimal.

If the time of oscillation is longer than the integration time:

(T

p

 > T

n

 (T

n

 is e.g. 240 seconds))

1. Increase T

n

 to 1.2 times T

p

2. Wait until the system is in balance again

3. If there is still oscillation, reduce K

p

 by e.g. 20%

4. Wait until the system is in balance

5. If it continues to oscillate, repeat 3 and 4

If the time of oscillation is shorter than the integration time:

(T

p

 < T

n

 (T

n

 is e.g. 240 seconds))

1. Reduce K

p

 by e.g. 20% of the scale reading

2. Wait until the system is in balance

3. If it continues to oscillate, repeat 1 and 2.

©Danfoss A/S (AC-MCI / sw), 2014-03 

DKRCC.PS.RP0.A1.02/520H7142 

 15

14 

DKRCC.PS.RP0.A1.02/520H7142 

©Danfoss A/S (AC-MCI / sw), 2014-03

Manual                      Superheat controller type EKD 316

Manual                      Superheat controller type EKD 316 

Finding the optimum settings

Details on the controller algorithm and settings

Kp factor (n04) and Kp min (n19)

The Proportional Gain is dependent on the value of the measured 

superheat SH relative to Reference superheat SH ref. The 

Proportional Gain has the following values relative to superheat SH:

If SH is more than 2.5K greater than SH ref, then Gain equals Kp 

factor.

If SH is within the range -0.5 and 2.5K from SH ref, then Gain equals 

Kp factor times Kp min.

The reason for this variable Gain is to provide stable superheat for 

values near the superheat reference. 

 Note:

 

The value of Gain does not change suddenly but gradually when 

SH gets close to SH ref.

Initial "Kick start" startup

In general the valve opening degree is controlled by the measured 

value of the superheat SH. This means that during certain 

situations during startup, the valve will be slow to open due to 

the built-up of superheat from a small value. To prevent this from 

happening, the valve is given an initial opening degree dependent 

on the Kp factor, the measured superheat SH and SH close, as 

given in the following relationship:

Initial OD% = kp factor*(SH – SH close)

This procedure is not to be confused with the force opening of the 

valve given in the “Problems with startup” section.

Dan

fo

ss

84N375.11

Dan

fo

ss

84N376.11

Problems with startup

Sometimes in one-to-one applications, the valve does not open 

sufficiently on startup, and troublesome low pressure trips may 

occur. This problem is typical when using the single loop control 

where only the SH controls the opening of the valve.

The 

force opening of valve

 function has been implemented in 

the EKD 316 controller. After startup, this function will provide a 

constant, set minimum opening degree during a set time period, 

regardless of the superheat value. The setting parameters are 

called 

Start OD%

 (n17) and 

StartUp time

 (n15). 

Please observe that the 

Start OD%

 is a minimum value after 

startup and if the measured superheat (u21) produces a value 

greater than 

Start OD%

 then the value will be valve opening 

degree (u24) – see the diagram.

Dan

fo

ss

84N378.11

Troubleshooting

Symptom

Possible Cause

Remedy

Suction pressure too low

Pressure drop across the evaporator too high

Lack of subcooling ahead of expansion valve

Check refrigerant ahead of expansion valve.

If the valve is placed much higher than condenser outlet, 

check pressure difference.

Evaporator superheat too high

1.  Check superheat performance, the settings  

 

SH min and SH max.

2.  Check valve capacity.

3.  Check that the maximum number of steps of  

 

valve is same as parameter n37.

Pressure drop across the expansion valve less than valve is 

sized for

Check pressure drop across expansion valve. Replace with 

larger valve.

Expansion valve too small

Check refrigeration system capacity and compare with 

expansion valve capacity. Replace with larger valve if 

necessary.

Expansion valve block with foreign material 

Remove valve and examine the orifice.

Evaporator wholly or partly iced up

De-ice evaporator

Liquid hammer 

in compressor

Superheat of expansion valve too low

Increase the values of SH close and SH min.

Superheat reference set too low

Increase the value  of  SH min

The S2 sensor not in good contact with the suction line

Ensure that S2 sensor is secured on suction line. Insulate 

sensor.

Alarms

Symptom

Possible Cause

Fault Message

Remedy

All Light emitting diodes 

flashing

E24

S2 sensor fault

E25

S4 sensor fault  

Analog input outside range.

E19

Pressure transmitter outside range.  

E20

Check pressure transmitter, connections at 14-15 and 

pressure.

No refrigerant selected

A11

Select refrigerant

Battery alarm

A44

Check the battery voltage is the nominal voltage.

The controller can give the 

following messages

Error message

E1

Fault in controller

E24

S2 Sensor error

E25

S4 Sensor error

E19

The input signal on terminals 21-22 is outside the range.

E20

The input signal on terminals 17-19 is below 

minumum limit (P0 signal)

Alarm message

A11

No refrigerant has been selected

A44

Battery alarm (no voltage or too low voltage)

Status codes

S5

MOP

S10

Refrigeration stopped  r12=off

non

Regulation, no fault

 Note:

1.  Only one alarm is displayed at a time in the controller display and are shown in the 

order given above. All alarms are displayed in the AKM system.

2.  The alarm E19 will only be active if address o10 is set to 1 or more.

3.  EKD 316 with change over relay ( 3 terminals 24-25-26)

4.  The battery alarm A44 is only active when battery alarm address A34 is set to ON.

Proportional Gain

Reg.OD%

OD%

Start OD%

Start

Start Up time*

Time from start 

Normal Reg.

Valve OD%

Forced OD%

Kp factor

Kp factor multiplied Kp min.

SH ref

-0.5

2.5

SH

Start

Time

Kp factor* (SH - SH Close)

When Kp factor = 3, SH = 12, Close = 2

Initial OD % = 30% 

OD%

Summary of Contents for EKD 316

Page 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Page 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Page 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Page 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Page 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Page 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Page 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Page 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Page 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Page 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Page 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Page 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Reviews: