Danfoss EKD 316 Manual Download Page 6

Operation

Superheat function

You may choose between two kinds of superheat regulation, 

either:

 

ƒ

Minimum stable superheat (MSS)

 

ƒ

Load-defined superheat

The regulation modes for controlling superheat

There are two different ways of controlling superheat, i.e. 

controlling according to the minimum stable superheat (MSS) and 

Load Defined superheat.

The parameter SH mode selects the controlling form where it can 

be set to MSS when set to 1, or Load Defined superheat when set 

to 2.

Minimum stable superheat (MSS)

The superheat control algorithm will attempt to regulate the 

superheat down to the lowest stable value between the minimum 

superheat setting, "Min SH" and the maximum superheat setting, 

"Max SH".

The superheat reference SH ref is adaptive and adjusted.

When using this form of control, there are three settings that have 

major affect on this mode of control.

Max SH – The maximum limit of SH ref. 

Min SH – The minimum limit of SH ref. Care should be taken not 

to set this value too low in order to avoid flooding back into the 

compressor.

Stability – This factor determines how much instability can be 

accepted. Small values will cause the SH ref to increase if the 

slightest instability in SH is detected.  Higher values will accept a 

higher degree of instability.

Function

Parameter

Default value

Superheat control -MSS

n21

1

Min Superheat Reference

n10

1 - 12 K

Max Superheat Reference

n09

2 - 15 K

Load define application

SH ref follows a defined curve as shown below. This curve is 

defined by three values: SH close SH max and SH min.

This form of regulation is similar to the thermostatic valve where 

the spring force can be adjusted to keep the SH (superheat) in the 

stable region to the right of the curve.

The advantage over the thermostatic valve is that there are three 

settings to define the operating curve.

The reference follows a defined curve. This curve is defined by 

three values: the closing value, the min. value and the max. value. 

These three values must be selected in such a way that the curve 

is situated between the MSS curve and the curve for average 

temperature difference 

Tm (temperature difference between 

media temperature and evaporating temperature.

Setting example = n22=4, n10=6 and n09=10 K).

Function

Parameter

Value

Superheat control mode -2 

= Load define

n21

Min Superheat Reference

n10

1 K

Max Superheat Reference

n09

2 K

Value of min. SH ref for loads 

under 10%

n22

Must be between 

Min and Max SH

Using the MOP

In order to reduce the current to the compressor it is possible to 

control the maximum operating pressure of the evaporator.

Evaporator pressure exceeds the "MOP" limit, the valve opening 

degree is controlled by the MOP function which will keep the 

pressure below the "MOP" limit. This function takes precedence 

over the superheat control, so during MOP control the superheat is 

not controlled.

The MOP function (address n11) is active when it is set to values 

less than 200 bar (200 bar corresponds to off). The pressure value 

is converted to the corresponding temperature value and when 

the MOP is active, the controller will prevent the evaporating 

temperature T1 from exceeding this value.

If Maximum Operating suction Pressure MOP  parameter n11 is 

reset from factory setting 20 to 1 bar (gauge) From the MOP i.e 1 

bar point the OD increases slower and slower until the pressure 

reaches MOP + 0.5 i.e 1.5 bar.  Subsequently the OD decreases 

rapidly as the pressure increases.

Function

Parameter

Value

Maximum operating pressure 

MOP

n11

0-200 bar

©Danfoss A/S (AC-MCI / sw), 2014-03 

DKRCC.PS.RP0.A1.02/520H7142 

 11

10 

DKRCC.PS.RP0.A1.02/520H7142 

©Danfoss A/S (AC-MCI / sw), 2014-03

Manual                      Superheat controller type EKD 316

Manual                      Superheat controller type EKD 316 

Valve definition
Valve type

Display EKA 164A Valve type

Display EKA 164A

n03

0 =  ETS 12.5, ETS 25, KVS 15

1 =  ETS 50, CCM 10, CCM 20, CCM 30

2 =  ETS 100, CCM 40

3 =  ETS 250, KVS 42

4 =  ETS 400

25

50

100

250

400

5 = user-defined

6 =  Saginomiya UKV/SKV/VKV/PKV

7 =   ETS 6

8 = CCMT 2, CCMT 4, CCMT 8

uSr

SA9

6

CC

Working range for pressure transmitter

Depending on the application a pressure transmitter with a given working range is used.
For the range of (-1 to 12 bar), the min. value is set to -1 bar

o20

MinTransPres.

For the range of (-1 to 12 bar), the max. value is set to 12 bar

o21

MaxTransPres.

Pressure transmitter

The range of the pressure transmitter can be set by entering the 

transmitter’s minimum value at address o20 and maximum value 

at address o21. The pressure sensor input is set up by default to 

accept an AKS 32R pressure transducer. If another sensor is to be 

used, it is important to note that it needs to be a 5 V ratiometric 

type (10%-90% of supply voltage). 

The default range for the typical pressure transducer is 0 to 16 bar. 

This can be changed by setting the minimum transducer pressure, 

"o20 MinTransPres", and the maximum transducer pressure, "o21 

MaxTransPres", to the new values.

Settings and checks to be made before 

start

Basic settings

Before using the EKD 316 controller, there are settings that have to 

be made for each individual application. These are the refrigerant 

type, the pressure transducer range and the total number of steps 

for the ETS valve. 

It is good practice and in some cases necessary to set the Main 

Switch r12 to OFF when making these changes. 

If terminal 20-21 has been used as a start/stop regulation, then the

interaction between internal and external start/stop function is, as 

shown on the following table:

Internal  

Start/stop

External  

start/stop (DI)

Regulation

Sensor 

monitoring

Configuration 

settings

Off

Off

=>

Off

No

Yes

Off

On

=>

Off

No

Yes

On

Off

=>

Off

Yes

No

On

On

=>

Yes

Yes

No

Refrigerant type

It is possible to choose from a list of 37 different refrigerants in the 

controller. 

If the refrigerant is not found on the list, it is possible to enter the 

Antione constants for the unlisted refrigerant using MODBUS 

communication and setting o30 to 13.

ETS valve type

It is important to select the right valve type as listed under Valve

definition. On using external display EKA 164A, the valve selection

will be displayed as 25, 50, 100, 250, 400, uSr, Sa9, 6 and CC. 

The number of steps and steps/sec can also be set in the controller 

at addresses n37 and n38 respectively:

In practise, the EKD 316 external display can only manage three 

digits. Therefore the set value at address n37 is always 10 times 

greater, i.e. if n37 is set to 263 then the true value is 2630. The same 

applies to the n37 address in the MODBUS communication system.

Refrigerant setting

Before refrigeration can be started, the refrigerant must be defined. 

You can select the following refrigerants:

o30

1 =  R12

2 =  R22

3 =  R134a

4 =  R502

5 =  R717

6 =  R13

7 =  R13b1 

8 =  R23

9 =  R500

10 =  R503

11 =  R114

12 =  R142b

13 =  User-defined 

14 =  R32

15 =  R227

16 =  R401

17 =  R507

18 =  R402A 

19 =  R404A

20 =  R407C 

21 =  R407A

22 =  R407B

23 =  R410A

24 =  R170

25 =  R290

26 =  R600

27 =  R600a 

28 =  R744

29 =  R1270

30 =  R417A

31 =  R422A

32 =  R413A

33 =  R422D

34 =  427A

35 =  R438A

R36 = Opteon XP10

37 =  R407F

(

 

Warning

: Wrong selection of refrigerant may cause damage to the compressor).

Start of controller

When the electric wires have been connected to the controller, the 

following points have to be attended to before the regulation starts:

1.  Switch off the external ON/OFF switch that starts and stops the 

regulation.

2.  Follow the menu survey in Appendix I, and set the various 

parameters to the required values.

3.  Switch on the external switch, and regulation will start.

4.  Follow the actual superheat on the display. 

Pressure Pe

MOP + 0.5

MOP

OD

At this pressure the OD

increases slower and

slower.

At this pressure the OD

no longer increases.

Beyond it the OD 

decreases.

Summary of Contents for EKD 316

Page 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Page 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Page 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Page 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Page 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Page 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Page 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Page 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Page 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Page 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Page 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Page 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Reviews: