Manual                      Superheat controller type EKD 316

Manual                      Superheat controller type EKD 316 

Dimensions

Ordering

Type

Function

Code no.

EKD 316

superheat controller 

(with terminals)

084B8040

EKA 164A

Display

(with MODBUS communication)

084B8563

EKA 183A

Programming key

084B8582

Supply voltage

24 V a.c./d.c.  +/-15% 50/60 Hz, 10 VA

(the supply voltage is not galvanically  

separated from the input and output signals)

Power consumption

Controller

ETS  step motor

5 VA

1.3 VA

Input signal 

*)Ri: mA: 400 ohm 

             V: 50 kohm

Current signal *

4-20 mA or 0-20 mA

Voltage signal *

0-10 V or 1-5 V

Pressure transmitter AKS 32R
Digital input from external contact function

Sensor input

2 pcs. Pt 1000 ohm

DI : < 800 ohm 

 ON

DI : > 30 kohm 

 OFF

Alarm relay

1 pcs. SPDT

AC-1: 4 A (ohmic)

AC-15: 3 A (inductive)

Step motor output

Pulsating 30 - 300 mA 

Data communication

Mounted with MODBUS data communication

Environments

0 to +55°C, during operations

-40 to +70°C, during transport
20 - 80% Rh, not condensed
No shock influence/vibrations

Enclosure

IP 20

Weight

300 g

Montage

DIN rail

Operation

External display type EKA 164A or AK-ST via 

data communication and system unit

Approvals

EU Low Voltage Directive and EMC demands re. 

CE-marking complied with.

LVD-tested acc. to EN 60730-1 and EN 60730-2-9

EMC-tested acc. to EN50081-1 and EN 50082-2

Battery backup

If battery backup is used, the requirements for 

the battery are: 18-24 V d.c. See also page 12. 

Max. distance between 

controller and valve

30 m

Accessories

Pressure transducer

Temperature sensor

External display

Programming key

AKS 32R, NSK

AKS 21, AKS 11

EKA 164A

EKA 183A

Necessary connections

Terminals:

1-2

Supply voltage 24 V a.c./d.c.

 

A dedicated transformer must be used.

3-4

Battery (the voltage will close the ETS valve if the 

controller loses its supply voltage).  

The battery voltage must not be connected from terminals 1 

and 2.

Danfos

s

84B3083.10

24V 18V

Connections

ETS/KVS

White

5

Black

6

Red

7

Green

8

ETS 6/

Saginomiya valves

Orange

5

Yellow

6

Red

7

Black

8

5-8

Supply to stepper motor

9-13 

Operation via data communication

EITHER EKA 164A OR System unit + software.

It is important that the installation of the data communication 

cable be done correctly.  

Cf. separate literature No. RC8AC...

20-21

Switch function for start/stop of regulation. 

 

Note:

If a switch is not connected, terminals 20 and 21 must be short 

circuited.

Application-dependent connections

Superheat control

14-15

Pt 1000 sensor at evaporator outlet (S2)

15-16

Pt 1000 sensor for measuring air temperature (S4)

17-19

Pressure transmitter type AKS 32R 

 

Note:

The signal can 

not

 be shared with other controllers

Control of the valves opening degree with analog signal

21-22

Current signal or voltage signal from other regulation 

(Ext. Ref.) 

24-26  Alarm relay

There is connection between 24 and 26 in alarm situa tions.

Connections

Connection to earth will destroy the controller

 1,2  

3,4    21,22

Class II

  

Warning

Any external connection with grounding could create a ground 

loop through a diode in the rectifier bridge which could destroy 

the power supply in EKD 316.

Data

Summary of Contents for EKD 316

Page 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Page 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Page 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Page 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Page 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Page 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Page 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Page 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Page 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Page 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Page 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Page 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Reviews: