Danfoss EKC 223 User Manual Download Page 18

Configuration

DI input configuration

The digital inputs DI1 and DI2 can be configured for multiple functions and the table below shows the options and

the polarity of the digital input signals.

Table 7: DI input configuration

Function

Description

Polarity

DI1

DI2

Value

o02

o37

DI Status

Only a status of the digital input.

Closed = ON

Open = OFF

*

*

1

Door function

When door is opened, cooling and fan is stopped but they will

resume when the door alarm delay expires.

Closed = Door is closed

Open = Door is open

*

*

2

Door alarm

When door is opened, cooling and fan is stopped and they will

not resume operation when the door alarm delay expires.

Closed = Door is closed

Open = Door is open

*

*

3

Main switch

Used for starting and stopping control.

Closed = Normal control

Open = Stop control

*

*

4

Night setback

Used to put controller into night mode.

Closed = Night mode

Open = Day mode

*

*

5

Reference offset

Used to add a reference offset to the thermostat setpoint.

Closed= Reference is offset

Open = No offset

*

*

6

External alarm

Used to generate alarm from an external signal.

Closed = No alarm

Open = Alarm

*

*

7

Defrost start

Used to initiate a defrost cycle (toggle switch).

From open to closed:

Defrost cycle is started

*

*

8

Pulldown cycle

Used to initiate a temperature pull down cycle (toggle switch). From open to closed:

Pulldown cycle is started

*

*

9

Sc sensor

A Sc condenser sensor is used to monitor the condensing tem-

perature.

Not applicable

*

10

Alarm codes

In an alarm situation the display will alternate between readout of the actual air temperature and readout of the

alarm codes of active alarms. There are two kinds of alarms - it can either be an alarm occurring during the daily

operation, or there may be a defect in the installation. A-alarms will not become visible until the set time delay has

expired. E-alarms, on the other hand, will become visible the moment the error occurs.

Here are the messages that may appear:

Table 8: Alarm codes

Code

Alarms

Description

Network alarm

E29

Sair sensor error

Air temperature sensor is defect or electrical connection is lost

--- Sair Error

E27

Def sensor error

S5 Evaporator sensor is defect or electrical connection is lost

--- S5 Error

E30

Sc sensor error

Sc Condenser sensor is defect or electrical connection is lost

--- Sc Error

A01

High temp alarm

Air temperature in cabinet is too high

--- High t.alarm

A02

Low temp alarm

Air temperature in cabinet is too low

--- Low t. Alarm

A99

High Volt alarm

Supply voltage is too high (compressor protection)

--- High Voltage

AA1

Low Volt alarm

Supply voltage is too low (compressor protection)

--- Low Voltage

A61

Condenser alarm

Condenser temp. too high - check air flow

--- Cond Alarm

A80

Cond. block alarm

Condenser temp. too high - manual reset of alarm required

(1)

--- Cond Blocked

A04

Door alarm

Door has been open for too long

--- Door alarm

A15

DI Alarm

External alarm from DI input

--- DI Alarm

A45

Standby Alarm

Control has been stopped by "r12 Main switch"

--- Standby mode

(1)

The condenser block alarm can be reset by setting r12 Main switch OFF and ON again or by powering down the controller.

(1)

The condenser block alarm can be reset by setting r12 Main switch OFF and ON again or by powering down the controller.

Control status

The controller has a special control status parameter which tells what the controller is doing. This parameter can be

readout in the display as parameter “u00 Control state” and this can provide valuable information to a service

technician to understand what the controller is doing.

Case controller, type EKC 223 and EKC 224

© Danfoss | Climate Solutions | 2023.05

BC432222569027en-000201 | 18

Summary of Contents for EKC 223

Page 1: ...User Guide Case controller Type EKC 223 and EKC 224 SW Ver 1 0x For refrigerated display cabinets cold storage rooms and simple heating applications...

Page 2: ...r contact function 9 Defrost 9 Start of defrost 9 Coordinated defrost via network 10 Defrost on demand 10 Applications 11 EKC 224 applications 11 EKC 223 applications 11 Wiring diagrams 12 EKC 224 12...

Page 3: ...iguration 23 Thermostat 24 Alarm settings 24 Defrost 25 Fan 26 Compressor 27 Miscellaneous 27 Polarity 28 Service 29 EKC 223 224 display menu 29 Configuration 29 Thermostat 30 Alarm settings 30 Defros...

Page 4: ...rdering 36 Certificates declarations and approvals 37 Certificates declarations and approvals 37 Online support 38 Case controller type EKC 223 and EKC 224 Danfoss Climate Solutions 2023 05 BC43222256...

Page 5: ...buttons a big display easy and intuitive menu structure and pre defined applications ensure ease of use Controller is loaded with energy efficiency features like smart evaporator fan management day n...

Page 6: ...line programming of the EKC controllers It can also perform production line programming of multiple controllers and show on line trend curves on selected parameters Finally KoolProg can also load cont...

Page 7: ...mpressor can be initiated based on this temperature Voltage protection The voltage protection ensures that the compressor motor is operating within safe voltage ranges If the power supply voltage gets...

Page 8: ...high condensing temperature Sc temperature C Sc temperature C Manual reset Block limit Pre alarm limit Pre alarm OK Compressor Pre alarm Block alarm T1 T2 T3 T4 Danfoss 80G8376 Change of temperature r...

Page 9: ...is used to control a solenoid that lets the hot gas flow through the evaporator The compressor is kept running to generate hot gas Start of defrost A defrost can be started in different ways Interval...

Page 10: ...and 1 Based on compressor runtime when the aggregate compressor runtime has passed a set time a defrost will be started Figure 11 Based on compressor runtime Danfoss 80G8459 Defrost start t 2 Based on...

Page 11: ...DI1 and DI2 can be configured for multiple functions and DI1 can also be configured for a condenser temperature sensor Sc 1 The digital inputs DI1 and DI2 can be configured for multiple functions and...

Page 12: ...DO1 1 Sair S5 Sc DI1 DI2 DO2 DO3 DO4 GND GND Danfoss 80G8433 5 6 7 3L 4N 10 11 12 13 14 8 9 2L 115 230 V 115 230 V 3 DO1 1 Sair S5 Sc DI1 DI2 DO2 DO3 DO4 GND GND Danfoss 80G8434 5 6 7 3L 4N 10 11 12 1...

Page 13: ...es in to the connectors allowed tightening torque and wire sizes are Power connectors wire size 0 5 1 5 mm2 max tightening torque 0 4 Nm Low voltage signal connectors wire size 0 15 1 5 mm2 max tighte...

Page 14: ...is ON but via the parameter P75 the alarm relay action can be inverted DO3 3L 6 Digital output signal Fan and Light There is connection between terminal 3L and 6 when the function is ON DO4 3L 7 Digi...

Page 15: ...r when the compressor is stopped and to the need of liquid receivers before the compressors Your local Danfoss agent will be pleased to assist with further advice etc Integration into network systems...

Page 16: ...st be plugged into the RS 485 adapter Figure 15 Connection of RS 485 adapter Danfoss 80G8451 Wiring The Modbus cable must be wired as shown in Figure 16 Figure 16 Modbus cable Danfoss 80G8440 B MODBUS...

Page 17: ...e network For the EKC controllers the system manager can via internal schedules control the day night status light status and defrost including coordinated defrost among multiple controllers Table 6 O...

Page 18: ...may be a defect in the installation A alarms will not become visible until the set time delay has expired E alarms on the other hand will become visible the moment the error occurs Here are the messag...

Page 19: ...in drip off delay S10 Control has been stopped by r12 Main switch S11 Compressor is stopped due to thermostat cut out S14 Defrost cycle is in progress S15 Fan delay after defrost S17 Door is open S20...

Page 20: ...lways operative The display keys will be locked automatically when not used for some time and the keyboard must be unlocked by pressing the arrow up and arrow down keys at the same time Key operations...

Page 21: ...is in progress Pud A temperature pulldown cycle has been initiated Err The temperature cannot be displayed due to a sensor error Shown in top of display The parameter value has reached max Limit Show...

Page 22: ...tion and select the function associated to digital input 2 see DI input configuration Press SET Open the o62 Quick setting parameter and select the presetting that fits with the application in use see...

Page 23: ...ering is used It will come out of pull down based on time and temperature defined under parameter r96 and r97 or can be stopped manually by pressing pull down push button on front panel 10 Sc condense...

Page 24: ...so be accomplished with the external switch function connected to a DI input Stopped refrigeration will give a Standby alarm 1 ON Start 0 OFF Stop 1 SEr Manual control of outputs allowed r13 r13 Night...

Page 25: ...roller contains a timer function that is zeroset after each defrost start The timer function will start a defrost if when the interval time is passed The timer function starts after voltage is connect...

Page 26: ...becomes larger than required Here you set how large a slide of the S5 temperature can be allowed When the value is passed a defrost will start The function can only be used in 1 1 systems when the eva...

Page 27: ...mode When the input is short circuited there will be regulation for night operation 6 rFd reference displacement Value in r40 is added to the reference r00 when the input is short circuited 7 EAL exte...

Page 28: ...ays on 1 dAn day night 2 doo based on door action 3 nEt Network signal from system manager o39 o39 Light remote Light remote Parameter used by the network system manager to control the light status On...

Page 29: ...olenoid valve Status on relay for cooling u59 u59 Fan relay Fan relay Status on relay for fan u60 u60 Def Relay Defrost relay Status on relay for defrost u62 u62 Alarm relay Alarm relay Status on rela...

Page 30: ...K R W r02 Max limitation of setpoint setting r03 105 0 50 0 C R W r03 Min limitation of setpoint setting 40 0 r02 35 0 C R W r04 Adjustment of the display s temperature readout 10 0 10 0 0 0 K R W r0...

Page 31: ...is set to 0 Fan Table 25 Fan Code Short text manual Min Max De fault Unit R W EKC 224 Appl EKC 223 Appl 1 2 3 4 1 2 3 4 F Fan F01 Fan at stop of compressor 0 FFC Follow comp 1 Fao ON 2 FPL Fan pulsin...

Page 32: ...st stop on time 6 Room MT El defrost stop on temp 7 Room LT El defrost stop on temp 0 7 0 R W o67 Replace the controllers factory settings with the present set tings 0 No 1 Yes 0 No R W o91 Display at...

Page 33: ...relay 0 Off 1 On 0 Off R u63 Light relay 0 Off 1 On 0 Off R u80 Firmware version readout R u82 Controller code no R u84 Heat relay 0 Off 1 On 0 Off R U09 Sc Condenser temperature 100 0 200 0 0 0 R Da...

Page 34: ...g range 40 105 C 40 221 F Controller accuracy 1 K below 35 C 0 5 K between 35 25 C 1 K above 25 C Type of action 1B relay Output DO1 Relay 1 16 A 16 16 A EN 60730 1 10 FLA 60 LRA at 230 V UL60730 1 16...

Page 35: ...ear side of the panel Slide the clips towards mounting surface until controller is firmly fixed To remove the controller unlatch the snapping tab and pull the clips backwards Dimensions Figure 24 Dime...

Page 36: ...AC 3 relays 084B4054 084B4154 EKC 224 Danfoss 80G8446 SET V V V S M pack 115 V AC 4 relays 084B4055 084B4155 S M pack 230 V AC 4 relays 084B4056 084B4156 EKA 206 Danfoss 80G8461 RS 485 Network adapter...

Page 37: ...have any questions Certificates declarations and approvals Table 32 Certificates declarations and approvals Controller Certification Mark Country EKC 223 224 EMC LVD RoHS CE EU EKC 223 224 UL recogni...

Page 38: ...ations manuals and guides 3D models and drawings case stories brochures and much more Start searching now at www danfoss com en service and support documentation Danfoss Learning Danfoss Learning is a...

Reviews: