ID
Parameter Name
A230.x
Setting range
Factory
Unit
Own
settings
11116
High limit Y2
1, 4
0.0 ... 999.9
999.9
11117
Low limit Y1
1, 4
0.0 ... 999.9
999.9
11118
Low T out X2
1, 4
-60 ... 20
-15
°C
11119
High T out X1
1, 4
-60 ... 20
15
°C
11141
Ext. input
1, 2, 4
OFF ; S1 ; S2 ; S3
; S4 ; S5 ; S6 ; S7
; S8
OFF
11142
Ext. mode
1, 4
COMFORT ;
SAVING ; FROST
PR. ; CONST. T
COMFORT
-||-
2
COMFORT ;
SAVING
COMFORT
11147
Upper difference
1, 4
OFF, 1 ... 30
OFF
K
11148
Lower difference
1, 4
OFF, 1 ... 30
OFF
K
11149
Delay
1, 4
1 ... 99
10
Min
11150
Lowest temp.
1, 4
10 ... 50
30
°C
11174
Motor pr.
1, 2, 4
OFF, 10 ... 59
OFF
Min
11177
Temp. min.
1, 4
10 ... 150
10
°C
-||-
2
-30 ... 50
0
°C
11178
Temp. max.
1, 4
10 ... 150
90
°C
-||-
2
-30 ... 70
30
°C
11179
Summer, cut-out
1, 4
OFF, 1 ... 50
20
°C
11182
Infl. - max.
1, 4
-9.9 ... 0.0
-4.0
-||-
2
-9.9 ... 0.0
0.0
11183
Infl. - min.
1, 4
0.0 ... 9.9
0.0
-||-
2
0.0 ... 9.9
4.0
11184
Xp
1, 4
5 ... 250
120
K
-||-
2
5 ... 250
80
K
11185
Tn
1, 4
1 ... 999
50
Sec
-||-
2
1 ... 999
30
Sec
11186
M run
1, 4
5 ... 250
60
Sec
-||-
2
5 ... 250
35
Sec
11187
Nz
1, 4
1 ... 9
3
K
-||-
2
1 ... 9
2
K
11189
Min. act. time
1, 2, 4
2 ... 50
10
11301
High T max Y2
1
0.0 ... 75.0
25.0
m/s
-||-
2
-10.0 ... 40.0
25.0
°C
11303
Low T max Y1
1
0.0 ... 75.0
0.0
m/s
-||-
2
-10.0 ... 40.0
5.0
°C
11327
Input type
4
OFF ; ON
OFF
11392
Sum. start, month
1, 4
1 ... 12
5
11393
Sum. start, day
1, 4
1 ... 31
20
156 | © Danfoss | 2017.05
VI.LG.H4.02
Operating Guide ECL Comfort 210/296/310, application A230