MENU > Settings > Alarm
High X
1x608
Definition of which voltage value corresponds to which position value.
The voltage (as a 0 - 10 volt signal) comes from a position measuring in
M1 and is applied to input S11 (ECA 32). This input voltage is converted to
display a % value for the position of M1.
See also "Position" and "Low X".
See Appendix “Parameter ID overview”
X
= Volt
Y
= Position
# 1 # = High X
MENU > Settings > Alarm
Alarm high
1x614
When the measured value gets higher than the set value, the alarm will
be activated.
See Appendix “Parameter ID overview”
Value:
Set the alarm value
MENU > Settings > Alarm
Alarm low
1x615
When the measured value gets lower than the set value, the alarm will be
activated.
See Appendix “Parameter ID overview”
Value:
Set the alarm value
MENU > Settings > Alarm
Alarm time-out
1x617
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.
See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
150 | © Danfoss | 2017.09
VI.GU.L2.02
Operating Guide ECL Comfort 210/296/310, application A275/A375