DMS Manual

Electrical

connections

Motor thermistors

If the motor is fitted with thermistors these may

be connected directly to the DMS. To connect the

thermistors, first remove the shorting link, and then

connect the thermistors between terminals 31A & 31B.

Use double-isolated thermistors to

retain PELV.

Serial communication

The DMS can be equipped with either AS-i or

Profibus communication capabilities.

The AS-i and Profibus interfaces are optional.

The AS-i Fieldbus is connected at terminals 125 & 126.

The details of the Profibus connectivity are given

at the end of the manual.

NB!:

Communications and control cabling should

not be located within 300mm of power

cabling. Where this cannot be avoided

consideration should be given to providing magnetic

shielding to reduce induced common mode voltages,

for example, by laying the communication and

control cables in a separate conduit.

Earthing

Ensure that the DMS unit is earthed

properly. Use the chassis earth studs

provided for the purpose (4 of size M4).

For type T73 units, an external earth plug

(size M8) is provided to facilitate earthing.

To retain the IP rating of DMS, remember

to close all the unutilized cable entries

using the gland plugs (bungs) provided

loose with the DMS unit. In units with external plugs,

all plugs must be correctly mounted.

High voltage warning

The voltage of the DMS is dangerous

whenever the equipment is connected to

the mains. Ensure the DMS is correctly

connected and that all safety measures have been

taken before switching on the supply.

Galvanic isolation (PELV)

All control terminals, and terminals for serial

communication are safely isolated from

the mains potential, i.e. they comply with

the PELV requirements of EN/ IEC 60947-1. PELV

isolation of the control card is guaranteed provided

there is max. 300 VAC between phase and earth.

MG.05.A2.02 - VLT is a registered Danfoss trademark

7

Summary of Contents for DMS 300

Page 1: ...lutions www danfoss com drives OperatingInstructions Decentral Motor Starter DMS 300 Decentral Motor Starter DMS 300 Operating Instructions 175R0901 MG05A202 REV 2003 05 06 XREF__BC NOT LOADED ON RIP...

Page 2: ...unication 7 Earthing 7 High voltage warning 7 Galvanic isolation PELV 7 Electrical Schematic 8 Setting up DMS 9 Adjustment Settings 9 Start stop profile setting 9 Start stop profile setting table 9 Tr...

Page 3: ...ions 16 Fuses 17 Order code format 18 Special variants 19 Motor connection 19 Details of Profibus Connectivity 20 Profibus DP Slave 6 E DC 24 V 4 A DC 24 V 1A 20 Table of bits in control and status wo...

Page 4: ...ied out 2 The COASTING STOP INVERSE command applied to the DMS does not disconnect the equipment from the mains and thus is not to be used as a safety switch It is the responsibility of the user or th...

Page 5: ...Centre punch for motor mounted versions if not already mounted on a motor Wall mounting For best cooling the DMS unit should be mounted vertically If needed horizontal mounting is allowable For instal...

Page 6: ...enclosure to limit heat rise in the enclosure to maintain the internal enclosure temperature at or below 40 deg C Heat loss of DMS at rated current is 18 watts approx 40 50 60 70 80 90 100 FLC Tempera...

Page 7: ...r ST SB versions provide strain relief for power and control cables by using the cable support provided in the DMS unit as shown Power factor correction If a DMS is used with static power factor corre...

Page 8: ...cation and control cables in a separate conduit Earthing Ensure that the DMS unit is earthed properly Use the chassis earth studs provided for the purpose 4 of size M4 For type T73 units an external e...

Page 9: ...DMS Manual Electrical Schematic MG 05 A2 02 VLT is a registered Danfoss trademark 8...

Page 10: ...load current setting note 0 1Amps is always added internally 0 2A See table below Off FLC 0 1A Note Settings marked grey are applicable only in Extended versions Start stop profile setting Choose the...

Page 11: ...y calculated by the microprocessor This uses a sophisticated mathematical model to accurately reflect motor heat generation and dissipation during all stages of operation e g Starting Running Stopping...

Page 12: ...s not used FLC setting table DIP Switch bits Value Amps Example 1 for setting FLC 4 3 Amps Example 2 for setting FLC 2 9 Amps 2 B2 3 2 On Off 3 B3 1 6 Off On 4 B4 0 8 On On 5 B5 0 4 Off On 6 B6 0 2 On...

Page 13: ...t to stop NB If both Start CW Start CCW inputs are active together the motor will stop Brake Release For variants with Braking function only variants SB EB ER When a Start is initiated the DMS automat...

Page 14: ...t 0 1 No fault Fault No fault Fault No fault Fault D3 input Not used 0 1 Not used Not used Not used P0 parameter Not used P1 parameter Not used P2 parameter Not used P3 parameter Not used It is possib...

Page 15: ...e cause of the overload and let the motor cool before restarting Three 3 Motor Thermistor Trip Identify and correct the cause of motor overheating If no thermistors are connected to the DMS ensure the...

Page 16: ...romechanical Brake Supply output Electromechanical Brake Supply Output Terminals 122 123 180 VDC 1 0 A max The electromechanicalbrake supply output voltage is proportional to the mains supply voltage...

Page 17: ...frequency emissions Class B as per EN 55011 Electrostatic discharge 4 kV contact and 8 kV air discharge no effect on operation Radio frequency electromagnetic field 0 15 MHz to 1 0 GHz no effect on op...

Page 18: ...25A 415 VAC or equivalent HRC fuses Semiconductor fuses are required to meet UL C UL Certification Semiconductor fuses listed below are manufactured by Bussmann and should be ordered directly from Bus...

Page 19: ...DMS Manual Order code format MG 05 A2 02 VLT is a registered Danfoss trademark 18...

Page 20: ...10 Motor thermistor B 4 Electromechanical brake A PE Earth connection 5 Electromechanical brake B Example 2 Variant T22 or T62 DMS Extended unit with an integrated service switch The service switch c...

Page 21: ...x 2 5sq mm 203 DC 0 V 204 DC 24 V galvanic isolation isolation voltage DC 500 V between bus and electronics DC 2 5kV between module supply and inputs outputs Bus interface Bus system Profibus DP modul...

Page 22: ...0 1 1 1 1 x x x x x 1 0 1 1 1 x x x x x 2 1 0 1 1 x x x x x 3 0 0 1 1 x x x x x 4 1 1 0 1 x x x x x 5 0 1 0 1 x x x x x 6 1 0 0 1 x x x x x 7 0 0 0 1 x x x x x 8 1 1 1 0 x x x x x 9 0 1 1 0 x x x x 0...

Page 23: ...5 H Han 10E connector 19 High voltage warning 7 M Motor mounting 4 Motor thermistors 7 O Operation 12 Operation with AS i Interface 12 Order code format 18 P Power factor correction 6 Power Wiring 6 P...

Page 24: ...lutions www danfoss com drives OperatingInstructions Decentral Motor Starter DMS 300 Decentral Motor Starter DMS 300 Operating Instructions 175R0901 MG05A202 REV 2003 05 06 XREF__BC NOT LOADED ON RIP...

Reviews: