6.3
Connecting supply and return lines
1.
Connect the supply line pipe (red label) with a flexible hose connection and with all the necessary compo-
nents, see Flexible hoses, Page 19.
2.
Connect the return line pipe (blue label) with a flexible hose connection and with all the necessary compo-
nents including a filter.
3.
Insulate the supply and return lines all the way to the heat pump.
1
2
Position Description
6 kW
8kW
1
Supply line (red)
DN 20
DN 25
2
Return line (blue)
DN 20
DN 25
6.4
Noise and vibrations
6.4.1
Installation of the heat pump
To prevent disturbing noise from the heat pump. the following recommendations should be observed:
•
In the event the heat pump is positioned on a vibration sensitive base, vibration dampers should be used. The
vibration dampers must be correctly dimensioned with regard to the heat pump's weight so that static spring
depression of at least 2 mm is obtained in all mounting components. Vibration dampers are available to pur-
chase as accessories.
•
Connection of the heat transfer fluid to the heat pump must be made using a flexible hose to prevent trans-
mission of vibration to building construction and the pipe system, see Flexible hoses, Page 19.
•
Ensure that pipes at lead-ins are not lying against the walls.
6.4.2
Flexible hoses
All pipes should be routed in such a way that vibrations cannot be transmitted from the heat pump through the
piping and continue into the building. This also applies to the expansion pipe. We recommend that flexible hoses
Installation and service instructions VMGFI202 – 19
Summary of Contents for DHP-AT
Page 1: ...Installation and service instructions DHP AT VMGFI202...
Page 4: ......
Page 35: ...11 Technical data Installation and service instructions VMGFI202 33...
Page 36: ...12 Connection diagram 34 Installation and service instructions VMGFI202...
Page 37: ...13 Wiring diagram Installation and service instructions VMGFI202 35...
Page 38: ...VMGFI202...