1.
2.
3.
4.
5.
-
-
-
5.8.4 Connecting the Sine-wave Filter to the Motor
Procedure
Strip a section of the outer cable insulation.
Fasten a connector/cable lug to the end of the stripped cable.
Create an electrical connection between the cable shield and ground by securing the stripped wire under the cable clamp.
Connect the ground cable to the nearest grounding terminal in accordance with the grounding instructions provided in
.
Connect the 3-phase AC motor cable to the sine-wave terminals U, V, and W.
If the enclosed drive has 1 sine-wave filter cabinet, run 1 set of motor cables to the cabinet.
If the enclosed drive has 2 sine-wave filter cabinets, run 2 sets of motor cables, 1 set to each sine-wave filter cabinet.
N O T I C E
Each sine-wave cabinet must have the same number of motor phase cables and they must be in quantities of 2
(for example, 2, 4, 6, or 8). 1 cable is not allowed. The cables are required to be equal length.
AQ262139143212en-000301 / 130R0879
104 | Danfoss A/S © 2021.10
Electrical Installation
VLT® AutomationDrive FC 302
Operating Guide
Summary of Contents for D9h
Page 2: ......