14 DKDHR 

VI.GP.N2.02 

Danfoss District Energy

Instructions   Water 

Heaters

12.0 Akva Lux II GW - Instructions

12.1 General

Variants

PLEASE NOTE that your water heater may look different than the wa-

ter heater shown, as variants with other components may be supplied. 

The control function, however, is basically as decribed below.

Maintenance and setting

The cover can be removed without using tools. For separation and 

cleaning of plate heat exchanger see page 18.

12.2 Description

The water heater is based on a gasketed stainless steel plate heat ex-

changer. The domestic hot water is prepared in a  heat exchanger based 

on the flow principle and the temperature is controlled by a combined 

hydraulic and thermostatic self-acting controller PTC2+P controller with 

integrated differential pressure controller, which blocks the flow of pri-

mary and secondary side flow through the heat exchanger immediately 

after completion of the tapping process.

12.3 DHW temperature control

Danfoss PTC2+P controller (1) for DHW. The DHW temperature is adjusted 

by turning the lever towards  “+” (warmer) or “-” (colder). 

Start by turning the handle 

clockwise

 - until stop /until the handle can 

not be turned anymore. Then turn the handle 

counter-clockwise

 until 

the temperature of the tap water is approx. 48 ° C at normal use (7-8 l/

min). The temperature should never exceed 55 ° C to avoid lime scale 

precipitation. 

12.4 By-pass or circulation thermostat

Bypass thermostat (default).

As a standard the Akva Lux II GW is equipped with a bypass thermostat, 

Danfoss FJVR (2), which ensures that hot water is produced immedi-

ately, when tapping starts. It is recommended to set the thermostat 

in pos.3. If the water temperature rises too slowly it can be necessary 

to set the thermostat at higher value.

Alternatively a DHW circulation system must be installed.

Circulation thermostat / control change to circulation.

If the water heater is connected to the DHW recirculation system in the 

building, the FJVR thermostat (3) will function as a circulation thermostat 

and control the circulation water temperature, independently of the set 

DHW temperature. It is recommended to set the thermostat in pos 3. 

For recirculation connection please refer to page 11 and 12.

The photo to the right shows a water heater, on which circulation hose 

and capillary tube have been mounted and connected to the domestic 

hot water controller, enabling the temperature of the circulating water 

to be controlled by the FJVR thermostat.

 

12.5 Akva Lux II GW with Danfoss AVE

The AVE expansion unit absorbs the thermal expansion of water in the 

heat exchanger. A discharge pipe is not necessary.

For mounting of AVE on site the brass bow must be removed and the 

AVE with T-piece and non-return valve must be mounted as shown.

The AVE expansion unit must not be applied  to systems with domestic 

hot water circulation. 

For systems with DHW circulation the expansion 

unit must be replaced by a safety valve and a discharge pipe, which is 

piped directly into the floor drain, must be installed.

2

1

Handle for temperature setting

Summary of Contents for Akva Lux II

Page 1: ...GW Diagram example measurements and main components 6 9 0 Akva Vita II Diagram example measurements and main components 7 10 0 Mounting 8 10 1 Test and connections 8 10 2 Systems with domestic hot wat...

Page 2: ...qualization of potentials should be effected according to local regulations Warning of hot surfaces Parts of the water heater may become hot and hot surfaces can cause serious burns Please be extremel...

Page 3: ...ose all shut off valves before the water heater is connected to the household piping 03 IMPORTANT Tighten all connections as vibrations during trans port and handling may have caused leaks 04 For syst...

Page 4: ...ion cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instr...

Page 5: ...8 Insulation cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose...

Page 6: ...6 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instruction on page 14 Ac...

Page 7: ...ples 5 Brushed stainless steel cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instructions...

Page 8: ...valve on the DCWinlet The pump must be installed so that the pump is pumping water towards the water heater If a time controlled pump is used it is to be recommended that the circulation water temper...

Page 9: ...ater towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 in controll...

Page 10: ...ail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of union nu...

Page 11: ...towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 as shown Fig 4...

Page 12: ...s shown Fig 8 Demount capillary tube from T piece Fig 9 Demount capillary tube from bypass thermostat Fig 10 Mount M8 x 1 screw plug F in T piece Fig 11 Fit new capillary tube G on nipple B by means o...

Page 13: ...and Akva Les II are equipped with a by pass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermostat in pos 3 Ifthew...

Page 14: ...rculation thermostat Bypass thermostat default AsastandardtheAkvaLuxIIGWisequippedwithabypassthermostat Danfoss FJVR 2 which ensures that hot water is produced immedi ately when tapping starts It is r...

Page 15: ...ault As a standard the Akva Vita II is equipped with a bypass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermosta...

Page 16: ...heatexchangersweakinhibited acid solutions e g 5 formic acetic or phosphoric acid may be used Deacidificationofgasketedplateheatexhanger AkvaLuxIIGW See page 16 Measuresaftermaintenancework After main...

Page 17: ...t and be able to dissolve the fouling calification on the plates Great care must be taken to select a proper cleaning solution that does not damage plates or gaskets Example of cleaning 1 Drain produc...

Page 18: ...l compressed dimension The bolts must not be slackened or tightened indiscriminately They must be loosened tightened alternately on the left and right side and in a crosswise pattern Loosening and tig...

Page 19: ...the household piping REMEMBER to check all the mixer taps in the house Replace mixer tap or non return valve only Not enough pressure on the hot water Strainer in cold water meter or in the cold wate...

Page 20: ...e during tapping Calified heat exchanger Short circuiting of defective heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Poor cooling Calified hea...

Page 21: ...e used in accordance with our instructions EU Directives EMC Directive 2004 108 EEC EN 61000 6 1 2007 Electromagnetic compatibility Generic standard Immunity for residential commercial and light indus...

Page 22: ...technical regulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for...

Page 23: ...23 23 Danfoss District Energy VI GP N2 02 DKDHR Instructions Water Heaters...

Page 24: ...Produced by Danfoss Redan A S 02 2014 VI GP N2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: