Liquid Level Sensor, AKS 4100/4100U
• Connect the device to the power supply
(see the section "Electrical installation/
connection".
• Press
3 times.
• Press
• Press
or to select either SINGLE
or COAXIAL. Press to confirm.
• Press
to change the PROBE LENGTH.
Press to change the position of the
cursor.
Press to decrease the value or to
increase the value.
Press to confirm.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
• Press
to change of SCALE 4 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press
to change of SCALE 20 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete
8-second timeout
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
•
Press to confirm.
• Press
or to select either
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
You have the possibility of checking
your settings by pressing twice.
Press to return to
default screen.
Quick Setup (all values below are only examples)
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
Note:
The signal converter can be programmed with or without mechanical process connector assembled.
AKS 4100
SINGLE CABLE 5000 mm
(0%) 4 mA
4877 mm
(100%) 20 mA
120 mm