AKD 2800
Programming
308 Terminal 53, analogue input voltage
(AI [V]53FUNCT.)
Value:
No function (NO OPERATION)
[0]
✭
Reference (REFERENCE)
[1]
Feedback (FEEDBACK)
[2]
Function:
In this parameter it is possible to select the function
required to be connected to terminal 53. Scaling of the
input signal is made in parameter 309
Terminal 53, min.
scaling
and parameter 310
Terminal 53, max. scaling
.
Description of choice:
No function
[0]. Is selected if the frequency converter
is not to react to signals connected to the terminal.
Reference
[1]. If this function is selected, the reference
can be changed by means of an analogue reference
signal. If reference signals are connected to more than
one input, these reference signals must be added up.
If a voltage feedback signal is connected, select
Feedback
[2] on terminal 53.
309
Terminal 53 Min. scaling
(AI 53 SCALE LOW)
Value:
0.0 - 10.0 Volt
✭
0.0 Volt
Function:
This parameter is used for setting the signal value
that is to correspond to the minimum reference or
the minimum feedback, parameter 204
Minimum
reference, Ref
MIN
/ 414
Minimum feedback, FB
MIN
.
Description of choice:
Set the required voltage value. For reasons of accuracy,
compensation should be made for voltage loss in long
signal cables. If the Time out function is to be used
(parameter 317
Time out
and 318
Function after time
out
), the value set must be higher than 1 Volt.
310
Terminal 53 Max. scaling
(AI 53 SCALE HIGH)
Value:
0 - 10.0 Volt
✭
10.0 Volt
Function:
This parameter is used for setting the signal value
that is to correspond to the maximum reference value
or maximum feedback, parameter 205
Maximum
reference, Ref
MAX
/ 414
Maximum feedback, FB
MAX
.
Description of choice:
Set the required voltage value. For reasons of
accuracy, compensation should be made for
voltage losses in long signal cables.
314 Terminal 60, analogue input current
(AI [MA] 60 FUNCT)
Value:
✭
No function (NO OPERATION)
[0]
Reference (REFERENCE)
[1]
Feedback (FEEDBACK)
[2]
Function:
This parameter allows a choice between the
different functions available for the input, terminal 60.
Scaling of the input signal is effected in parameter
315
Terminal 60, min. scaling
and parameter
316
Terminal 60, max. scaling
.
Description of choice:
No function
[0]. Is selected if the frequency converter
is not to react to signals connected to the terminal.
Reference
[1]. If this function is selected, the reference
can be changed by means of an analogue reference
signal. If reference signals are connected to more than
one input, these reference signals must be added up.
If one current feedback signal is connected, select
Feedback
[2] on terminal 60.
315
Terminal 60 Min. scaling
(AI 60 SCALE LOW)
Value:
0.0 - 20.0 mA
✭
0.0 mA
Function:
In this parameter you can set the signal value that will
correspond to the minimum reference or minimum
feedback, parameter 204
Minimum reference, Ref
MIN
/ 414
Minimum feedback, FB
MIN
.
Description of choice:
Set the required current value. If the Time out function is
to be used (parameter 317
Time out
and 318
Function
after time out
) the value set must be higher than 2 mA.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.H2.02 -
31