66
Capacity
controller RS8HE202 © Danfoss 2017-07
AK-PC 781A
Setup control of heat
recovery
1. Go to Configuration menu
2. Select heat recovery
3. Define heat recovery circuits
4. Define heat circuit requirement
for pressure variation
Press the +-button to go on to the
next page
In our example, we have selected
CO2 as the refrigerant. This opens
for the displayed settings. In our
example we have both a circuit
for hot tap water and a circuit for
heating.
3 -Heat recovery
Heat recovery mode (applies only when the refrigerant
selected is not CO2). See also page 109.
Choice of method for heat recovery
No: Heat recovery not used
Thermostat: Heat recovery operated from thermostat
Digital input: Heat recovery operated from signal on a
digital input.
Heat recovery relay
Choose whether an output is required that should be
activated during heat recovery.
Heat recovery ref
Reference for the condensing pressure, when heat
recovery is activated.
Heat recovery ramp down
Configure how quickly the reference for the condenser
pressure should be ramped down to normal level after
heat recovery. Configure in Kelvin per minute.
Heat recovery cutout
Temperature value where the thermostat cuts-out the
heat recovery.
Heat recovery cutin
Temperature value where the thermostat cuts-out the
heat recovery.
Heat recovery circuit (applies only when the refrigerant
selected is CO2). See also page 112.
Here you select which recovery circuits shall be regu-
lated:
- None
- Circuit for hot tap water
- Circuit for heating
- Both hot tap water and heating
4 - Heat reclaim type for heating
Here you define how the condensing pressure (HP) shall be
regulated when the recovery circuit for heating requires
heat:
- No HP offset (simple control)
- HP offset. Here the controller must receive a voltage sig-
nal. The offset values that apply to the max. value must be
defined in the heat circuit settings. See next page.
- Max heat reclaim. Here the controller must receive a volt-
age signal, but the regulation is increased to also control
the pump, fans and gas cooler bypass.
Configuration - continued
CO
2
HFC
Summary of Contents for AK-PC 781A
Page 39: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 39 Example continued ...
Page 42: ...42 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Page 90: ...90 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Page 133: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 133 ...