AK-LM 330 Vers. 1.4x
Menu operation RC8CC202 © Danfoss 09/2012
5
Pressostats 1 - 2
Measurements
AK error
When “ON”, the controller is in alarm condition.
No. of pressostats
The number of pressostats that have been defined can be read here.
1 to 2 can be read and operated in the following menus.
3 or more can only be read and operated from the Service Tool AK-ST 500.
P1 pressure.
Pressure reading for the transmitter defined in "Pressostat 1"
P1 actual state
The pressostat's actual value is shown here. ON or OFF.
2
There are similar readings for "Pressostat 2".
Settings
Main switch
Main switch:
ON: Regulation
OFF: Controller stopped
P1 Cut out pressure
Cut out value for relay "Pressostat 1"
P1 Cut in pressure
Cut in value for relay "Pressostat 1"
P1 High alarm limit
High alarm limit "Pressostat 1"
P1 High alarm delay
Delay time for high alarm "Pressostat 1"
P1 Low alarm limit
Low alarm limit "Pressostat 1"
P1 Low alarm delay
Delay time for low alarm "Pressostat 1"
P1 Sensor select
The transmitter that is to send the signal to "Pressostat 1" is defined here.
2
There are similar settings for "Pressostat 2".
Voltage inputs
Measurements
AK error
When “ON”, the controller is in alarm condition.
No. of voltage input
The number of voltage functions that have been defined can be read here.
1 to 2 can be read and operated in the following menus.
3 or more can only be read and operated from the Service Tool AK-ST 500.
V1 value
The voltage measurement for the function defined in "Volt 1"
V1 actual state
The function's actual value is shown here. ON or OFF.
2
There are similar readings for "Volt 2".
Settings
Main switch
Main switch:
ON: Regulation
OFF: Controller stopped
V1 Cut out
Cut out value for relay which is defined in "Volt 1"
V1 Cut out delay
Delay time for cut out of relay
V1 Cut in
Cut in value for relay which is defined in "Volt 1"
V1 Cut in delay
Delay time for cut in of relay
V1 High alarm limit
High alarm limit "Volt 1"
V1 High alarm delay
Delay time for high alarm "Volt 1"
V1 Low alarm limit
Low alarm limit "Volt 1"
V1 Low alarm delay
Delay time for low alarm "Volt 1"
V1 Volt signal type
The voltage area that is to send the signal to "Volt 1" is defined here.
0-5 V: Defined with setting = 9
1-5 V: Defined with setting = 11
0-10 V: Defined with setting = 10
2-10 V: Defined with setting = 12
(The received voltage is converted to a value which is defined by the following:
Lower voltage value = Min. read out. Higher voltage value = Max. read out.
It is these limits that form the function's setting values)
V1 Min read out
Definition of the reading at the voltage area's lowest value
V1 Max read out
Definition of the reading at the voltage area's highest value.
2
There are similar settings for "Volt 2".