background image

 02-2014 

RI8PG202

INSTRUCTIONS

AK-CC 250A

Data communication MOD-BUS: 

Coordinated defrost

t

amb

 = 0 - +55°C

230 V a.c.  50/60 Hz

2.5 VA

CE (250 V a.c.)

UL *** (240 V a.c.)

DO1. Refrigeration *

10 (6) A

10 A Resistive
5FLA, 30LRA

DO2. Defrost *

10 (6) A

10 A Resistive
5FLA, 30LRA

DO3. Fan or
          refrigeration 2 *

6 (3) A

6 A Resistive
3FLA, 18LRA
131 VA Pilot duty

DO4.  Alarm,  light,  rail  heat                
           or hotgas defrost *

4 (1) A
Min. 100 mA**

4 A Resistive
131 VA Pilot duty

* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must  be keept.

** Gold plating ensures make function with small contact loads

*** UL-approval based on 30000  couplings

 

 

10 V < U < 256 V

No

Function

Pt /PTC sensors

See page 6.

Reviews: