AHF 005/010
■
Environmental data
Permissible
temperature range*
During transport of the unit:
During storage of the unit:
During operation of the unit:
-13°F...+158°F (-25°C...+70°C) (to
VDE 0160)
-13°F...+131°F (-25°C...+55°C) (to
VDE 0160)
41°F...+104°F (5°C...+40°C) without
power derating
41°F...+131°F (5°C...+55°C) with
power derating
Humidity class*
Humidity class F without condensation ( 5% - 85% relative humidity)
Installation height h*
H
≤
3280 m altitude above sea level
3280 ft (1000 m) altitude above sea
level< h
≤
13,100 ft (4000 m) altitude
above sea level
without power derating
with power derating
Degree of pollution
VDE 0110 Part 2 degree 2
Insulation strength
Overvoltage category III according to VDE 0110
Packaging
DIN 55468 for transport packaging materials
Type of protection
IP 20
Approvals
CE: Low-Voltage Directive; UL; C-tick
*climatic conditions according to class 3K3
(EN 50178 Part 6.1)
MG.80.B4.22 - VLT is a registered Danfoss trademark