AHF 005/010
■
Ordering numbers, 380 - 415 V, 50 Hz
AHF 005 and AHF 010, 380V - 415V, 50Hz
Danfoss ordering number
Typical Danfoss adjustable frequency drive series
I
AHF,N
Typical Motor
Used [kW]
AHF 005
AHF 010
VLT 5000
VLT 6000 HVAC
VLT 8000 AQUA
10 A
4, 5.5
175G6600
175G6622
5006, 5008
6006, 6008
8006, 8008
19 A
7.5
175G6601
175G6623
5011
6011
8011
26 A
11
175G6602
175G6624
5016
6016
8016
35 A
15, 18.5
175G6603
175G6625
5022, 5027
6022, 6027
8022, 8027
43 A
22
175G6604
175G6626
5032
6032
8032
72 A
30, 37
175G6605
175G6627
5042, 5052
6042, 6052
8042, 8052
101 A
45, 55
175G6606
175G6628
5062, 5072
6062, 6072
8062, 8072
144 A
75
175G6607
175G6629
5102
6102
8102
180 A
90
175G6608
175G6630
5122
6122
8122
217 A
110
175G6609
175G6631
5152
6152
8152
289 A
132, 160
175G6610
175G6632
5202, 5252
6172, 6222
8202, 8252
324 A
175G6611
175G6633
370 A
200
175G6688
175G6691
5302
6272
8302
Higher ratings can be achieved by paralleling the filter units
434 A
250
Two 217A units
5352
6352
8352
578 A
315
Two 289 A units
5452
6402
8452
613 A
355
289 A and 324 A units
5502
6502
8502
648 A
400
Two 324 A units
6552
8602
Please note that the matching of the typical Danfoss adjustable frequency drive and filter is pre-calculated
based on 400V and assuming typical motor load (4- or 2-pole motor). VLT 5000 series is based on a max.
160 % torque application, while VLT 6000 and 8000 series are based on a max. 110% torque application.
The pre-calculated filter current may be different than the input current ratings of the VLT 5000, VLT 6000,
and VLT 8000 series as stated in the respective instruction manuals, as these numbers are based on
different operating conditions.