8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input)
and/or via the fieldbus.
[0]
Digital input
Activates Preset Reference selection via a digital input.
[1]
Bus
Activates Preset Reference selection via the serial communication port or fieldbus option.
[2]
Logic AND
Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally
via one of the digital inputs.
[3] *
Logic OR
Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of
the digital inputs.
NB!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
3.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communication via the FC Port.
8-80 Bus Message Count
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter shows the number of valid telegrams detected on the bus.
8-81 Bus Error Count
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter shows the number of telegrams with faults (e.g. CRC fault), detected on the bus.
8-82 Slave Message Count
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter shows the number of valid telegrams addressed to the slave, sent by the frequency
converter.
8-83 Slave Error Count
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter shows the number of error telegrams, which could not be executed by the frequency
converter.
3.9.7 8-9* Bus Jog
Parameters for configuring the Bus Jog.
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM* [0 - par. 4-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM* [0 - par. 4-13 RPM]
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.