1.1 Description
The 300 A and 500 A current sensor kits are designed for
D2h/D4h/D7h/D8hdrives in the power ranges shown in
Table 1.1
and
Table 1.2
. To identify the power rating, see
chapter 1.1.1 Identifying the Power Rating
.
Product group and series
Voltage rating
(V)
Power rating [kW
(hp)]
VLT
®
HVAC Drive FC 102,
VLT
®
Refrigeration Drive FC 103,
VLT
®
AQUA Drive FC 202
(T4) 380–480
110–200
(150–300)
(T7) 525–690
75–315
(75–350)
VLT
®
AutomationDrive FC 302
(T5) 380–500
90–160
(125–200)
(T7) 525–690
55–250
(75–350)
Table 1.1 Applicable Power Ranges for 300 A Current Sensor Kit
Product group and series
Voltage rating
[V]
Power rating [kW
(hp)]
VLT
®
HVAC Drive FC 102,
VLT
®
Refrigeration Drive FC 103,
VLT
®
AQUA Drive FC 202
(T4) 380–480
200–315
(300–450)
(T7) 525–690
200–400
(250–400)
VLT
®
AutomationDrive FC 302
(T5) 380–500
200–250
(300–350)
(T7) 525–690
160–315
(200–350)
Table 1.2 Applicable Power Ranges for 500 A Current Sensor Kit
1.1.1 Identifying the Power Rating
To find the drive power rating, use the following steps:
1.
Obtain the following information from the
nameplate, which is on the drive. Refer to
Illustration 1.1
.
•
Product group and drive series
(characters 1–6)
•
Power rating (characters 7–10)
•
Voltage rating (phases and mains)
(characters 11–12)
2.
Determine if the power rating is in
Table 1.1
and
Table 1.2
.
1
Product group and drive series
2
Power rating
3
Voltage rating (phases and mains)
Illustration 1.1 Example Nameplate
1.1.2 Kit Ordering Numbers
Kit number
Kit description
176F3752
300 A Current Sensor Conversion Kit
D2h/D4h/D7h/D8h
176F3737
500 A Current Sensor Conversion Kit
D2h/D4h/D7h/D8h
Table 1.3 Kit Numbers for 300 A and 500 A Current Sensor Kits
Installation Instructions
300 A/500 A Current Sensor Kit for
D2h/D4h/D7h/D8h Drives
VLT
®
FC Series FC 102, FC 103, FC 202, FC 302
Danfoss A/S © 07/2018 All rights reserved.
MI70V202