Wiring the Drive
05/2008
Danaher Motion
40
S200-VTS Product Manual
NOTE
For maximum ride through capability a 240 VAC input is recommended.
J1-7, J1-8, J1-9
or TB1-8,9,10
L3 240 VAC
L2 240/120 VAC
L1 240/120 VAC
Th
ese terminals connect 120/240 VAC power to
the drive’s output power stage BUS for motor
power.
For single-phase operation, 120/240 use inputs
J1-8, L2, and J1-9, L1.
Input Voltage Range (RMS)
S20260, S20360, S20660: 0 to 265 VAC
S21260, S22460: 120 to 265 VAC
Phases
1 or 3
Transformer
(recommended KVA if
transformer is required.)
S20260: 1.5 to 2 kVA
S20360: 2.0 to 3 kVA
S20660: 3.0 to 5 kVA
S21260: 4.5 to 6 kVA
S22460: 8.0 to 12 kVA
Maximum AC Line KVA
1
S20260, S20360, S20660: 100
S21260, S22460: 250
1
Maximum AC Line is specified to limit the mains surges to the drive.
Recommended Fusing
Line Inputs
S20260 S20360 S20660 S21260 S22460
Type – 250 VAC Time Delay Fuse
240 VAC 3 Phase
(ARMS)
Bussmann
FRN-R-5
Bussmann
FRN-R-8
Bussmann
FRN-R-15
Bussmann
JKS-20
Bussmann
JKS-30
240 VAC 1 Phase
(ARMS)
Bussmann
FRN-R -5
Bussmann
FRN-R-10
Bussmann
FRN-R-20
Bussmann
JKS-30
Bussmann
JKS-30
120 VAC 1 Phase
(ARMS)
Bussmann
FRN-R -5
Bussmann
FRN-R-10
Bussmann
FRN-R-20
NA NA