Danaher Motion
05/2008
Connector Pinout and DEscriptions
S200-CNS Product Manual
35
N O T E
8.4 TB1:
H
IGH
P
OWER
AC
P
OWER
C
ONNECTIONS
Models: S21260-xNS
The S200 AC input drives are capable of direct line operation. All units are fully isolated and do not
require external isolation transformers. The inrush current on the connection to the line is internally
limited to a safe level for the drive. There are no voltage selection or ranging switches required to
operate within the specified voltage input ranges.
TB1 High Power AC Units Power Connection
1 PE
Protective Earth (Motor Cable Shield Connection)
2 W
Motor Output Phase W
3 V
Motor Output Phase V
4 U
Motor Output Phase U
5 Regen Optional Regen Resistor Connection (See Wiring Detail Section)
6 - Bus Main DC Bus – Output (Normally not connected)
7 + Bus Main DC Bus + Output (Normally connected with Optional Regen)
8 L3
Mains L3 Incoming Power Connection
9 L2
Mains L2 Incoming Power Connection
10 L1
Mains L1 Incoming Power Connection
Please refer to the Specifications section for fusing and rating information.
The S200 series drives are functionally compatible with all standard forms of
three phase AC lines:
Grounded neutral WYE
Open-Delta Grounded Leg
TEE
NOTE
It is the customer’s responsibility to supply appropriate fuses or
circuit breakers in the TB1 AC drive power lines to comply with local
electrical codes.
Recommended Mating Connectors:
Spring Fork Lugs or M4 or #8 screws
Hollingsworth SS20948SF
Molex 19099-032
Or Equivalent
For maximum line droop tolerance connect logic power to 230Vac
instead of 115Vac
WARNING
After powering down the drive, monitor the BUS voltage by
connecting a meter from TB1-7 (+BUS) to TB1-6 (-BUS) to verify
the internal BUS capacitors have discharged prior to working on
the drive.
WARNING
The Regen input is not short circuit protected. The Regen
Resistance MUST be within specified ranges to prevent damage to
the drive. 15 Ohms minimum resistance for the S21260-xNS.
WARNING
Selected Regen Resistor must be able to handle constant 390Vdc
connection without risk of fire or must otherwise be thermally
protected with an overload device.
WARNING
Do not apply power or operate unit without the terminal block
cover in place.
PE
W
V
U
Regen
-Bus
+Bus
L1
L2
L3