Menu C : Allocation of the analog output
Access in STOP mode only
Functions to allocate to
one of the digital
outputs
Comments on the allocated function
Converter temp (NTC)
Relay nr. =
The allocated relay switches if the heatsink temperature
exceeds 70°C, tolerance ± 3°C..
Mains anomaly:
Relay nr. =
The mains voltage is compared to the value entered in
Menu B - part 1 and the allocated relay will switch if the
mains voltage is out of the tolerance of 480 V+10 %
respectively 200 V –15%.
SAN1:1=Fs, 2=Im,
3=N4=Pw, 5=Iw, 6=Us
Set here the parameter you want to allocate to the
analog output
SAN1
, T
ERMINAL
B
LOC
X2/41 – X2/42
•
1
for the output frequency: 10 V =
F
max
•
2
for the motor current :
10 V =
I
NOM
•
3
speed of the motor
10 V =
N
MAX
need the option “Speed Sense”
•
4
active output power
10 V =
P
MAX
of motor
•
5
active output current
10 V =
P
MAX
/
1.28
U
S
•
6
for output voltage:
10 V = last
U
S
/F
S
Pt.
SAN2:1=Fs, 2=Im,
3=N4=Pw, 5=Iw, 6=Us
Set here the parameter you want to allocate to the
analog output
SAN2
, T
ERMINAL
B
LOC
X2/69 – X2/70
Comp. level
(0-10) (V) =
Enter here you comparison level between 0 … 10 VDC.
This is the comparison value for AI1
Time delay
(s) =
Delay to trigger the output when the above comparison
level has been exceeded. Delay 0 … 5 s
Menu D: The parameters accessible in START mode
Access allowed in START mode
The following parameters have been described in the menu B. For complete
information please refer to
Menu B
Display
Description
Filter freq. ctrl
(1 to 10) =
1 to 10
Acceleration time
1 to 255 s – Values < the one of menu B are not accepted
Deceleration time
1 to 255 s – Values < the one of menu B are not accepted
Freq ctrl source
0=PC560 1=T.Bl.?
Keypad = 0, Terminal block = 1
MCM - 0 = Abs. 1 = SH
2 = DTO 3 = none?
The current monitoring function. Only the MCM value
selected through terminals X2/6 and X2/7 will be displayed
Courant
Iabs(A) =
A current
<
I
REF
Courant Ish(A) =
A sensitivity value
Courant
IDTO =
A dynamic factor between 0 and 300. In START a $ will be
displayed on pos. 18 / second line when the condition is
true, i.e. the allocated relay pulls.
FCC duration s) =
A time between 0 and 60 s
FCC current
IFCC(A) =
A current
≤
I
NOM
of the motor
Permanent current
IFCP(A) =
A current
≤
20% of
I
NOM
of the motor
Low freq. smoothing =
A smoothing factor between
0 and 250
Slip compensation =
A compensation factor between
0 and 254
S476-gb-0348
User Manual K4000