background image

 

www.dalemans.com

   

  

|

 

  

 

16

   

 

5. 

SPECIFICATIONS  

To guarantee safety and performance, any gas detection installation must be calibrated and maintained regularly 
according to the manufacturer’s guidelines. 

 

 
 
 
 

CHARACTERISTICS

 

Brand 

Design and manufacture 

 

DALEMANS S.A. 

Principle and gas 
concerned 

Measurement principle  

 

Catalytic 

Methane (CH4) 

 

0 - 100 % LEL 

Propane (C3H8) 

 

 0 - 100 % LEL 

Butane (C4H10)  

 

 0 - 100 % LEL 

Detection performance 

Response time (T90) 

 

< 30 s 

Accuracy  

 

± 2 % range < 50 % LEL 

Supply

 

Mains 

 

24V 

Power 

 

0.45 W ± 0.05 

Current 

 

 

18 mA ± 2

 

Secured 

  

12V 

Box 

Material 

 

Flame-retardant and UV-stable plastic (UL-94V0)

 

Dimensions (H

 

x

 

W

 

x

 

D

)

 

 

147 x 119 x 51 mm

 

Weight 

 

 

285 g

 

IP protection index

 

 

IP 65

 

Reversibility 

 

YES 

Standard fixing 

 

4 screws 

Connection 

Cable input 

 

1 x M20

 

Screwed terminal 

 

3 x 0.75 - 2.5 mm²

 

Outputs

 

Type 

 

1 x 3F

 

Output signal 

 

3-wire analogue voltage 

Conditions of use 

Temperature   

 

0 °C - +50 °C

 

Humidity  

 

  

10 - 90% RH (without condensation) 90

 

-

 

110KPa 

Certifications 

Licence

 

 

(ex) II 3G Ex nA d IIC T2 Gc Tamp: 0°C - +50°C

 

Danger zones

 

 

Zone 2

 

Standards

 

 

EN 60079-0, EN 60079-1, EN 60079-15

 

Cell unit certificate

 

 

FTZU 15 ATEX 00032 U

 

Marking 

 

CE, RoHS 

 

 

 

T

h

e

 i

n

fo

rm

a

ti

o

n

 co

n

ta

in

e

d

 i

n

 t

h

is 

d

o

cu

m

e

n

is 

n

o

n

-co

n

tr

a

ctu

a

a

n

d

 su

b

je

ct 

to

 ch

a

n

g

e

Summary of Contents for D-TEX3F+

Page 1: ......

Page 2: ...hibited Warning All information contained in this document is non contractual and subject to change without notice We also encourage you to regularly check the availability of a new version on our web...

Page 3: ...ALITY ASSURANCE 7 1 INTRODUCTION 8 1 1 Certification 8 2 DESCRIPTION 9 2 1 Overview 9 2 2 Dimensions 10 3 INSTALLATION 11 3 1 Positioning of the detectors 11 3 2 Assembly 12 3 3 Wiring 13 3 4 Electric...

Page 4: ...without help from DALEMANS may prevent the equipment from working correctly and as a result prevent guaranteeing the safety of the occupants of the installations being monitored The modification disa...

Page 5: ...e gases are typically 20 LEL for the first alarm level A1 and 40 LEL for the second level A2 The choice of alarm levels must consider the possible effects of local climatic conditions Temperature The...

Page 6: ...h a normal degree of safety 2 Gas groups Group Reference gas Definition I Methane Equipment intended for mines on the surface or under the surface IIA Propane Equipment intended for surface industries...

Page 7: ...cerning the collection and recycling of Waste Electrical and Electronic Waste WEEE These provisions aim to preserve the natural resources used to produce this product and to avoid the dispersal of sub...

Page 8: ...nce of this marking label the detector is not certified for use in danger zones Figure 1 identification and certification label Compliance Definition see Directive 2034 14 EU for more information II E...

Page 9: ...astic flame retardant box a certified cable gland a detection head with a flameproof enclosure and a connection terminal mounted on a circuit board The detection head and the D BASE 3F card are design...

Page 10: ...www dalemans com 10 2 2 Dimensions Figure 3 D TEX3F dimensions in mm D TEX3F...

Page 11: ...sources must be considered Consider possible combinations of gas sources and dissemination effects The detector must be protected against risks related to the operation of the installations The detec...

Page 12: ...rews and pins Make sure that dust deposits do not obstruct the sensor and that water does not enter the detector The D TEX3F may be mounted horizontally or vertically For vertical assembly the box s c...

Page 13: ...requirements of the D TEX3F detector are compatible with the characteristics of the measurement panel see Specifications Connections to the D TEX3F detector are via the 24V GND OUT terminal present o...

Page 14: ...s of sensitivity of the sensors This calibration must be carried out according to the procedure given by DALEMANS or by its local representative and in any case by qualified personnel having received...

Page 15: ...ilter Fault signal active on the panel Wiring or connection defective Sensor disconnected or defective Voltage in the detector between the 24V and GND terminals outside of limits 4 3 Spare parts and a...

Page 16: ...rent 18 mA 2 Secured 12V Box Material Flame retardant and UV stable plastic UL 94V0 Dimensions H xW x D 147 x 119 x 51 mm Weight 285 g IP protection index IP 65 Reversibility YES Standard fixing 4 scr...

Page 17: ...www dalemans com 17 Notes...

Page 18: ......

Reviews: