4.2. 

Error diagnosis  

Problem displayed on the alarm panel

 

Possible cause(s) 

 

Non-zero measurement 

 

  

Presence of gas possible. 

 

Non-zero measurement in the absence of gas. 

 

  

Detector calibration fault. 

 

Measurement too high or too low 

 

Zero measurement in the presence of gas. 

 

 

Wiring or connection defective. 

 

 

Voltage in the detector (between the “

24V

” 

and “

GND

” terminals) outside of limits. 

 

 

Sensor or filter obstructed (dust). 

 

 

Sensor or filter contaminated. Replace the 
sensor AND the filter. 

 

“Fault” signal active on the panel 

 

 

Wiring or connection defective. 

 

 

Sensor disconnected or defective. 

 

 

Voltage in the detector (between the “

24V

” 

and 

GND

” terminals) outside of limits. 

 

4.3. 

Spare parts and accessories  

Spare parts  

 

Reference 

 

Card D•BASE 3F+ with catalytic sensor CH

4

  

100% LEL

 

BASDLINE031 

 

Card D•BASE 3F+ with catalytic sensor C

3

H

8

 

100% LEL

 

BASDLINE032 

 

Card D•BASE 3F+ with catalytic sensor C

4

H

10

 

100% LEL

 

BASDLINE033 

 

Cover without face for detector D

•Tex3F & D•Can 

BOI00000237 

Accessories  

Reference  

Remote gas injection kit D•LINE 

 

ACCKIT00006 

 

Airtight protection kit IP65 D•LINE 

 

ACCKIT00007 

 

Collector cover D•LINE 

 

ACCKIT00008 

 

Airtight remote gas measurement kit D•LINE 

 

ACCKIT00009 

 

 

 

 

 

 

Summary of Contents for D-TEX3F+

Page 1: ......

Page 2: ...hibited Warning All information contained in this document is non contractual and subject to change without notice We also encourage you to regularly check the availability of a new version on our web...

Page 3: ...ALITY ASSURANCE 7 1 INTRODUCTION 8 1 1 Certification 8 2 DESCRIPTION 9 2 1 Overview 9 2 2 Dimensions 10 3 INSTALLATION 11 3 1 Positioning of the detectors 11 3 2 Assembly 12 3 3 Wiring 13 3 4 Electric...

Page 4: ...without help from DALEMANS may prevent the equipment from working correctly and as a result prevent guaranteeing the safety of the occupants of the installations being monitored The modification disa...

Page 5: ...e gases are typically 20 LEL for the first alarm level A1 and 40 LEL for the second level A2 The choice of alarm levels must consider the possible effects of local climatic conditions Temperature The...

Page 6: ...h a normal degree of safety 2 Gas groups Group Reference gas Definition I Methane Equipment intended for mines on the surface or under the surface IIA Propane Equipment intended for surface industries...

Page 7: ...cerning the collection and recycling of Waste Electrical and Electronic Waste WEEE These provisions aim to preserve the natural resources used to produce this product and to avoid the dispersal of sub...

Page 8: ...nce of this marking label the detector is not certified for use in danger zones Figure 1 identification and certification label Compliance Definition see Directive 2034 14 EU for more information II E...

Page 9: ...astic flame retardant box a certified cable gland a detection head with a flameproof enclosure and a connection terminal mounted on a circuit board The detection head and the D BASE 3F card are design...

Page 10: ...www dalemans com 10 2 2 Dimensions Figure 3 D TEX3F dimensions in mm D TEX3F...

Page 11: ...sources must be considered Consider possible combinations of gas sources and dissemination effects The detector must be protected against risks related to the operation of the installations The detec...

Page 12: ...rews and pins Make sure that dust deposits do not obstruct the sensor and that water does not enter the detector The D TEX3F may be mounted horizontally or vertically For vertical assembly the box s c...

Page 13: ...requirements of the D TEX3F detector are compatible with the characteristics of the measurement panel see Specifications Connections to the D TEX3F detector are via the 24V GND OUT terminal present o...

Page 14: ...s of sensitivity of the sensors This calibration must be carried out according to the procedure given by DALEMANS or by its local representative and in any case by qualified personnel having received...

Page 15: ...ilter Fault signal active on the panel Wiring or connection defective Sensor disconnected or defective Voltage in the detector between the 24V and GND terminals outside of limits 4 3 Spare parts and a...

Page 16: ...rent 18 mA 2 Secured 12V Box Material Flame retardant and UV stable plastic UL 94V0 Dimensions H xW x D 147 x 119 x 51 mm Weight 285 g IP protection index IP 65 Reversibility YES Standard fixing 4 scr...

Page 17: ...www dalemans com 17 Notes...

Page 18: ......

Reviews: