Page 34 of 51
SK2018 GLOBAL FDLA-V/P-AC-001
Buzzer
If a command is received by the fan coil unit, the master unit will respond with 2 beeps for each setting, while the slave unit
will respond with 1 beep.
Auto Restart
The system uses non-volatile memory to save the present operation parameters when system is turned off or in case of
system failure or cessation of power supply. Operation parameters are mode, set temperature, louver’s position, and the fan
speed. When power supply resumes or the system is switched on again, the same operations as previously set will function.
On/Off Switch on LED Display Panel
a)
This is a tact switch to select Cool→Heat→Off operation mode.
b)
In COOL mode, the set temperature of the system is 24ºC with auto fan speed. There are no timer and sleep modes.
c)
In HEAT mode, the set temperature of the system is 24ºC with auto fan speed. There are no timer and sleep modes.
d)
Master unit that does not use a wall pad will globally broadcast.
Electric Heater Safety Switch
Before the electrical heater is turned on, the EH safety switch must be closed and the fan must be working.
If this contact is opened
for ≥ 1 second or the fan is not working, the heater will be turned off immediately and report an
error and fan speed will change to high speed.
Once the contact is returned to the closed position ≥ 60 seconds, reset the error and the heater will start ag
ain.
When the EH safety switch is opened ≥ 3 times within 60 minutes the heater is not allowed to start anymore.
Turn off the unit to reset the fault, provided that the switch has returned to the closed position.
Low Temperature Protection of Indoor Coil in Winter
This is frost protection when the unit is off to prevent water from freezing in the coil.
If Unit with SW2=0 (2-pipe system), it is in Standby Mode
If Tr
≦
2 ºC for 2 minutes, MTV1 is turned on. AUX1 is on. If Ti1 < 5ºC for 2 minutes, EH (if present) is switched on. Indoor fan
is turned on at low speed. If Tr
≧
5ºC for 2 minutes, MTV1 is turned off. AUX1 is off. Electric Heater is turned off. Indoor fan is
switched off.
If Unit with SW2=1 (4-pipe system), it is in Standby Mode
If Tr
≦
2 ºC for 2 minutes, MTV2 is turned on. AUX1 is on. If Ti2 < 5ºC for 2 minutes EH (if present) is switched on. Indoor fan
is turned on at low speed. If Tr
≧
5ºC for 2 minutes, MTV2 is turned off. AUX1 is off. Electric Heater is turned off. Indoor fan is
switched off.
NOTE
When button pressing is effective, the master unit buzzer will beep twice and the slave unit will beep once.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...