SK2019 FCSD(H)-V/P-ECM-001
Configuration Settings
Note:
0 = OFF
1 = ON
SW1-SW5 Network address setting
DIPA-S1
DIPB-S2
SW5/SW6
Fan Qty setting
SW5=0 Single fan application
SW6=1
SW5=1 Twin fans application
SW7/SW8 Operating mode
SW7=0 Cooling and heating modes available
SW8=0
SW7=0 Cooling and heating modes available,
SW8=1 with EH functioning as booster
SW7=1 Cooling mode only available
Master / Slave setting
SW6=1 Master
SW6=0 Slave
Preheat temperature setting
SW4=1 28ºC
SW4=0 36ºC
230VAC on/off valve setting
SW3=1 With valve
SW3=0 No valve
2-pipe/4-pipe system configuration
SW2=1 4-pipe system
SW2=0 2-pipe system
PRO contact setting
SW1=1 Window contact (remote on/off)
When PROs closed for 10 minutes, unit
enters standby mode.
When PROs opened, unit resumes operation.
SW1=0 Economy contact
When PROs closed, dead-band condition is
increased from “Tr=Ts+/-1” to “Tr=Ts+/-4”.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...