Installation Guide

SIGN197 | GE2025-6710

Power Supply Features

•  Supports all 24 VDC Tetra Products

•  Dry and Damp Locations Rated

•  Class 2 Power Supply

•  120-277 VAC Input

 

WARNING / AVERTISSEMENT

RISK OF ELECTRIC SHOCK

•  Disconnect power at fuse box or circuit breaker before servicing or 

installing product.

•  Properly ground Tetra

®

 power supply.

•  Must be enclosed in an end product.
RISK OF FIRE

•  In the end product, power supply spacing to other heat producing 

components shall be minimum 2 inches spacing to sidewalls and 

minimum 2 inches spacing to top of enclosure.

•  Adjacent power supplies shall be spaced at least 1 in. end to end 

and 4 in. in any other direction.

•  Use only approved wire for input/output connection. Minimum size 

18 AWG (0.82 mm

2

).

•  Follow all local codes.

•  Application considerations potentially requiring additional spacing 

include high ambient temperature seen by the power supply, poor 

contact with a heat dissipating material, inadequate ventilation, or 

direct exposure to sun.

RISQUES DE DÉCHARGES ÉLECTRIQUES

•  Coupez l’alimentation électrique à la boîte de fusibles ou au disjoncteur avant 

l’entretien ou l’installation du produit.

•  Assurez-vous de correctement mettre à terre le bloc d’alimentation Tetra

®

.

•  Doit être inclus à l’intérieur d’un produit final.
RISQUES D’INCENDIE

•  Dans le produit fini, l’espacement entre le bloc d’alimentation et les autres 

composants dégageant de la chaleur doit être d’au moins 2 pouces des 

parois latérales et d’au moins 2 pouces du haut de l’enceinte.

•  Les blocs d’alimentation adjacents doivent être espacés d’au moins 1 po 

de bout en bout et 4 po dans toute autre direction.

•  N’utilisez que des fils approuvés pour les entrées/sorties de connexion. 

Taille minimum 18 AWG (0.82 mm

2

).

•  Respectez tous les codes locaux.

•  Certaines applications pourraient requérir un espacement additionnel, p. 

ex. une température ambiante élevée autour du bloc d’alimentation, un 

mauvais contact avec une matière dissipatrice de chaleur, une ventilation 

inadéquate ou une exposition directe au soleil. 

Save These Instructions

Use only in the manner intended by the manufacturer.

If you have any questions, contact the manufacturer.

Prepare Electrical Wiring

Electrical Requirements

•  Limited to use in dry and damp locations.

•  The suitability of rain enclosure shall be determined if 

intended for wet location.

•  The grounding and bonding of the LED Driver shall be 

done in accordance with National Electric Code (NEC) 

Article 600.

•  Follow all National Electric Codes (NEC) and local codes.

Tetra

®

 LED Systems Power Supply

GEPS24-25U-NA (120-277 VAC input/24VDC output/25W)

24

Volt

BEFORE YOU BEGIN

Read these instructions completely and carefully.

 

CAUTION / ATTENTION

RISK INJURY

•  While performing installations described, gloves, safety 

glasses or goggles should be worn.

RISQUES DE BLESSURE

•  Lors de l’exécution des installations décrites, des gants, des lunettes 

de sécurité ou des lunettes de protection doivent être portées.