8.3.7. Earthing
The F.G pin in
a
circle Connector must be wired to the F.G terminal of the SMPS.
Earth pin on LAN1 and LAN2 is a signal Shield.
Earth wire should be used more than 2 mm.
The length of the ground line is as short as possible.
AC Power Earth and control system Ground are must be isolated.
Master
Slave
Master
Slave
√
[Figure 8-18]
Earth wiring methods
8.3.8. Ethernet wiring
The following pin assignment is used for the DTP7-L Ethernet master.
RJ45
26pin
receptacle pin
name
Description
1
14
Tx+
Transmit Data +
2
15
Tx-
Transmit Data -
3
23
Rx+
Receive Data +
6
24
Rx-
Receive Data -
shield
21
Cable shield
Functional earth
[Table 8-1] Ethernet connector map
8.3.9. Ethernet cable
DTP10-L Ethernet communication cable recommended specification
Cable minimum requirements
: CAT.5E STP
Recommended: over CAT6
Plug: STP CAT.5E RJ-45 8P8C
(Metal materials)
※
you should connect the shield between the cable and the plugs.
In case of use the FTP / STP cable, you should use the Metal plug to connect the plug the shield and
ground wires.
[Figure 8-19] FTP metal cable plug