Troubleshooting by Indication on the Remote Controller
88
3.18
CC
Humidity Sensor System
Abnormality
Remote Controller Display
CC
Applicable Models
FXFQ
Method of Error Detection
Even if an error occurs, operation still continues.
Error is detected according to the moisture (output
voltage) detected by the moisture sensor.
Error Decision Conditions
When the moisture sensor is disconnected or short
circuited
Supposed Causes
Defective sensor
Disconnection