Outline of Control (Indoor Unit)
SiME341909EA
80
Part 4 Functions and Control
8.10 Electronic Expansion Valve Control
Electronic expansion valves in indoor units have the functions of conducting superheating
degree control in cooling operation. However, if the indoor units receive any control command
such as a protection control command or a special control command from the outdoor unit, the
units will give a priority to the control command.
• Superheating degree control in cooling operation
This function is used to adjust the opening of the electronic expansion valve so that
superheating degree (SH), which is calculated from the detection temperature (Tg) of the gas
pipe thermistor (R3T) and the detection temperature (Tl) of the liquid temperature thermistor
(R2T) of the indoor unit, will come close to a target superheating degree (SHS).
At that time, correction to the superheating degree is made according to the differences (ΔT)
between set temperature and suction air temperature.
SH = Tg – Tl
where,
SH: Evaporator outlet superheating degree (°C)
Tg: Indoor unit gas pipe temperature (R3T)
Tl: Indoor unit liquid pipe temperature (R2T)
SHS (Target superheating degree)
• Normally 5°C.
• As ΔT (Remote controller set temp. – Suction air temp.) becomes larger, SHS becomes lower.
• As ΔT (Remote controller set temp. – Suction air temp.) becomes lower, SHS becomes larger.
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...