SiME341909EA
Outline of Control (Indoor Unit)
Part 4 Functions and Control
79
Note(s)
8.9 Dew Condensation Prevention Control
8.9.1 FXFSQ-AR Models
Indoor operation under a certain condition will limit the swing range of the flaps.
Refer to the table below for flap action under this control.
8.9.2 FXAQ-AR Models
In cooling and dry operation, the following control is carried out in order to prevent dew
condensation when the horizontal blade blows air downward.
Starting condition
Dew condensation prevention control
Dry operation with horizontal airflow (Position
C
) is carried out for 1 hour.
When there is any change to fan operation, airflow direction and operation ON/OFF state during
dew condensation prevention control, this control is canceled.
Dew condensation prevention control
Flap setting
OFF
In action
P0
P0
P1
P1
P1
P1
P2
P2
P2
P3
P3
P3
P4
P4
P4
Swing
P0 – P4
P1 – P4
Thermostat OFF
De
w
condensation
pre
v
ention control OFF
De
w
condensation
pre
v
ention control in action
Position P0 contin
u
es
for 30 min
u
tes.
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(O
b
ser
v
ed horizontally)
FXAQ-AR
Position
A
P4
B
(minutes)
20
Position
C
P3
● Horizontal blade is set to downward flow (Position
A
)
● Cooling operation (compressor operation) continues for
B
minutes.
&
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(O
b
ser
v
ed horizontally)
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...