Special Control
SiME341909EA
68
Part 4 Functions and Control
Note(s)
7. Special Control
7.1 Outdoor Unit Rotation
In the case of multi-outdoor-unit system, this outdoor unit rotation is used to prevent the
compressor from breaking down due to unbalanced oil level between outdoor units.
Details of outdoor unit rotation
In the case of multi-outdoor-unit system, each outdoor unit is given an operating priority for the
control.
Outdoor unit rotation makes it possible to change the operating priority of outdoor units.
Thus, the system becomes free of compressors that stop over an extended period of time at the
time of partial loading, preventing unbalanced oil level.
Timing of outdoor unit rotation
OR
After oil return control
At the beginning of the startup control
There are outdoor units that stop operation.
Low pressure of all outdoor units in operation is less than 0.25 MPa.
Example) The following diagram shows outdoor unit rotation in combination of 3 outdoor units.
Cooling
1. “Master unit”, “slave unit 1” and “slave unit 2” in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are
different from “master unit” and “slave unit” for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be
designated as master unit.
Consequently, The LED display on the main PCB for “master unit”, “slave unit 1” and “slave unit
2” do not change.
Normal control
Priority
1
Priority
2
Priority
3
Priority
3
Priority
1
Priority
2
Normal control
Master Slave 1 Slave 2
Master
Slave 1 Slave 2
Startup
control
Outdoor unit
rotation
Oil return
control
Outdoor unit
rotation
Normal control
Priority
1
Priority
2
Priority
3
Normal control
Priority
2
Priority
3
Priority
1
Master Slave 1 Slave 2
Master Slave 1 Slave 2
·
There are outdoor
units that stop
operation.
OR
·
Low pressure of all
outdoor units in
operation < 0.25 MPa.
Outdoor unit
rotation
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...